![Daikin RXL25G2V1B Service Manual Download Page 105](http://html.mh-extra.com/html/daikin/rxl25g2v1b/rxl25g2v1b_service-manual_501970105.webp)
Troubleshooting
SiENBE04-925_A
90
Service Diagnosis
4.13 Four Way Valve Abnormality
Remote Control
Display
EA
Method of
Malfunction
Detection
The room temperature thermistor, the indoor heat exchanger thermistor, the outdoor
temperature thermistor, and the outdoor heat exchanger thermistor are checked if they function
within their normal ranges in each operation mode.
Malfunction
Decision
Conditions
A following condition continues over 1 ~ 10 minutes (depending on the model) after operating
for 5 ~ 10 minutes (depending on the model).
Cooling / Dry
(room thermistor temp. – indoor heat exchanger temp.) < –5°C
Heating
(indoor heat exchanger temp. – room thermistor temp.) < –5°C
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
SIENBE04-925_A_FRONT.pdf 105
24/02/2011 13:53:56
Summary of Contents for RXL25G2V1B
Page 8: ...SiENBE04 925_A vi Table of Contents ...
Page 14: ...Introduction SiENBE04 925_A xii ...
Page 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Page 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 20: ...Specifications SiENBE04 925_A 6 Specifications ...