![Daikin RXL25G2V1B Service Manual Download Page 110](http://html.mh-extra.com/html/daikin/rxl25g2v1b/rxl25g2v1b_service-manual_501970110.webp)
SiENBE04-925_A
Troubleshooting
Service Diagnosis
95
Troubleshooting
Check No.04
Refer to P.118
Check No.06
Refer to P.120
Check No.07
Refer to P.121
Check No.08
Refer to P.121
Check No.09
Refer to P.122
(R11897)
Caution
Replace the fan motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 09
Check the outdoor fan.
Check No. 08
Check the discharge
pressure.
Check No. 04
Check the electronic
expansion valve.
Check No. 06
Check the outdoor heat
exchanger thermistor.
Check No. 07
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
SIENBE04-925_A_FRONT.pdf 110
24/02/2011 13:53:56
Summary of Contents for RXL25G2V1B
Page 8: ...SiENBE04 925_A vi Table of Contents ...
Page 14: ...Introduction SiENBE04 925_A xii ...
Page 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Page 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 20: ...Specifications SiENBE04 925_A 6 Specifications ...