Daikin RXL25G2V1B Service Manual Download Page 1

SiENBE04-925_A

Service 

Manual

Inverter Pair

Wall Mounted Type G-Series

[Applied Models]

z

 Inverter Pair: Heat Pump

SIENBE04-925_A_FRONT.pdf   1

24/02/2011   13:53:43

Summary of Contents for RXL25G2V1B

Page 1: ...SiENBE04 925_A Service Manual Inverter Pair Wall Mounted Type G Series Applied Models z Inverter Pair Heat Pump ...

Page 2: ...SiENBE04 925_A Service Manual Inverter Pair Wall Mounted Type G Series Applied Models z Inverter Pair Heat Pump ...

Page 3: ...SiENBE04 925_A Table of Contents i Inverter Pair Wall Mounted Type G Series zHeat Pump Indoor Units FTXL20G2V1B FTXL25G2V1B FTXL35G2V1B Outdoor Units RXL20G2V1B RXL20G2V1B9 RXL25G2V1B RXL35G2V1B ...

Page 4: ...ostat Control 26 1 7 NIGHT SET Mode 27 1 8 ECONO Operation 28 1 9 2 Area INTELLIGENT EYE Operation 29 1 10 Inverter POWERFUL Operation 31 1 11 Other Functions 32 2 Function of Thermistor 33 3 Control Specification 34 3 1 Mode Hierarchy 34 3 2 Frequency Control 35 3 3 Controls at Mode Changing Start up 37 3 4 Discharge Pipe Temperature Control 39 3 5 Input Current Control 40 3 6 Freeze up Protectio...

Page 5: ...it 82 4 7 Unspecified Voltage between Indoor Unit and Outdoor Unit 83 4 8 Outdoor Unit PCB Abnormality 84 4 9 OL Activation Compressor Overload 86 4 10 Compressor Lock 87 4 11 DC Fan Lock 88 4 12 Input Overcurrent Detection 89 4 13 Four Way Valve Abnormality 90 4 14 Discharge Pipe Temperature Control 92 4 15 High Pressure Control in Cooling 94 4 16 Compressor System Sensor Abnormality 96 4 17 Posi...

Page 6: ...197 3 5 Removal of Reactor Partition Plate 205 3 6 Removal of Sound Blanket 207 3 7 Removal of Four Way Valve 209 3 8 Removal of Compressor 212 4 Outdoor Unit RXL25G2V1B 214 4 1 Removal of Outer Panels 214 4 2 Removal of Electrical Box 216 4 3 Removal of PCB 221 4 4 Removal of Drain Pan Heater 226 4 5 Removal of Sound Blanket 228 4 6 Removal of Outdoor Fan Fan Motor 230 4 7 Removal of Thermistors ...

Page 7: ...ng 269 2 3 Jumper and Switch Settings 270 3 Application of Silicon Grease to a Power Transistor and a Diode Bridge 271 Part 9 Appendix 272 1 Piping Diagrams 273 1 1 Indoor Unit 273 1 2 Outdoor Unit 274 2 Wiring Diagrams 276 2 1 Indoor Unit 276 2 2 Outdoor Unit 276 ...

Page 8: ...SiENBE04 925_A vi Table of Contents ...

Page 9: ... power cable plug from the plug socket before disassembling the equipment for repair Working on the equipment that is connected to the power supply may cause an electrical shook If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits do not touch any electrically charged sections of the equipment If the refrigerant gas is discharged during the repair wo...

Page 10: ...n electrical shock Do not clean the air conditioner by splashing water Washing the unit with water may cause an electrical shock Be sure to provide the grounding when repairing the equipment in a humid or wet place to avoid electrical shocks Be sure to turn off the power switch and unplug the power cable when cleaning the equipment The internal fan rotates at a high speed and cause injury Be sure ...

Page 11: ... heat generation or fire When wiring between the indoor and outdoor units make sure that the terminal cover does not lift off or dismount because of the cable If the cover is not mounted properly the terminal connection section may cause an electrical shock excessive heat generation or fire Do not damage or modify the power cable Damaged or modified power cable may cause an electrical shock or fir...

Page 12: ...vent children from swallowing it If a child swallows the coin battery see a doctor immediately Warning Caution Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site to prevent electrical shocks Do not install the equipment in a place where there is a possibility of combustible gas leaks If the combustible gas leaks and remains around the ...

Page 13: ...ure to install the packing and seal on the installation frame properly If the packing and seal are not installed properly water may enter the room and wet the furniture and floor For unitary type only Caution Icon Type of Information Description Note Note A note provides information that is not indispensable but may nevertheless be valuable to the reader such as tips and tricks Caution Caution A c...

Page 14: ...Introduction SiENBE04 925_A xii ...

Page 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...

Page 16: ... after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check COMFORT AIRFLOW Operation Anti Corrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Drain Pan Heater Indoor Unit Quiet Operation Flexibility Multi Split Split Type Compatible Indoor Unit NIGHT QUIET Mode Automatic Flexible Voltage Correspondence OUTDOO...

Page 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...

Page 18: ...Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 12 0 12 0 11 0 13 0 13 0 12 0 12 0 12 0 11 0 13 0 13 0 12 Power Consumption Rated W 26 26 26 28 28 28 26 26 26 28 28 28 Power Factor 98 5 94 2 98 5 97 9 93 6 97 2 98 5 94 2 98 5 97 9 93 6 97 2 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D mm 295 800 215 2...

Page 19: ...d Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 11 0 11 0 10 0 14 0 14 0 13 0 12 0 12 0 11 0 15 0 14 0 14 Power Consumption Rated W 24 24 24 30 30 30 26 26 26 32 32 32 Power Factor 99 2 94 9 100 0 97 4 93 2 96 2 98 5 94 2 98 5 97 0 99 4 95 2 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D mm 295 800 215 295 800...

Page 20: ...Specifications SiENBE04 925_A 6 Specifications ...

Page 21: ...ENBE04 925_A Printed Circuit Board Connector Wiring Diagram 7 Part 3 Printed Circuit Board Connector Wiring Diagram 1 Printed Circuit Board Connector Wiring Diagram 8 1 1 Indoor Unit 8 1 2 Outdoor Unit 11 ...

Page 22: ...r swing motors 6 S46 Connector for display PCB 7 S47 Connector for signal receiver PCB 8 H1 H2 H3 FG Connector for terminal board 9 JA Address setting jumper Refer to page 268 for detail JB Fan speed setting when compressor stops for thermostat OFF JC Power failure recovery function auto restart Refer to page 270 for detail 10 LED A LED for service monitor green 11 FU1 F1U Fuse 3 15 A 250 V 12 V1 ...

Page 23: ...E04 925_A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 9 PCB Detail PCB 1 Control PCB V1 FU1 S1 S41 S21 S47 JB JA JC S46 S25 LED A S32 FG H1 H2 H3 2P206687 1 ...

Page 24: ...tor Wiring Diagram SiENBE04 925_A 10 Printed Circuit Board Connector Wiring Diagram PCB 4 INTELLIGENT EYE Sensor PCB PCB 2 Signal Receiver PCB PCB 3 Display PCB 3P210728 1 S48 3P210728 1 RTH1 SW1 S49 LED3 LED2 LED1 S26 3EB86013 1 ...

Page 25: ...Fuse 20 A 250 V 8 V2 V3 Varistor 1 S10 Connector for filter PCB 2 S20 Connector for electronic expansion valve coil 3 S30 Connector for compressor 4 S40 Connector for overload protector 5 S50 Connector for magnetic relay 6 S70 Connector for fan motor 7 S80 Connector for four way valve coil 8 S90 Connector for thermistors outdoor temperature outdoor heat exchanger discharge pipe 9 HL3 HN3 Connector...

Page 26: ...iENBE04 925_A 12 Printed Circuit Board Connector Wiring Diagram PCB Detail PCB 1 Filter PCB PCB 2 Main PCB E1 E2 V2 FU3 HL1HN1 S S50 on main PCB HL2 S11 HN2 HR1 3P203203 1 V3 S10 S20 2P203198 1 J5 S90 S50 S40 S70 LED A FU2 V1 S80 HL3 HR2 HN3 S30 FU1 ...

Page 27: ...lter PCB 2 S20 Connector for electronic expansion valve coil 3 S40 Connector for overload protector 4 S50 Connector for magnetic relay 5 S70 Connector for fan motor 6 S80 Connector for four way valve coil 7 S90 Connector for thermistors outdoor temperature outdoor heat exchanger discharge pipe 8 S100 Connector for forced operation button PCB 9 HL3 HN3 Connector for filter PCB 10 HR2 Connector for ...

Page 28: ...it Board Connector Wiring Diagram PCB Detail PCB 1 Filter PCB PCB 2 Main PCB PCB 3 Forced Operation Button PCB HR1 HL2 3P254234 1 FU1 HN2 S FU3 AC2 E1 E2 AC1 S11 V3 V2 S50 on main PCB S10 J5 S90 FU2 S100 S50 2P254206 1 S70 S40 S20 S80 HL3 HN3 V1 LED A U VW HR2 SW1 S110 3P255755 1 ...

Page 29: ...nector for fan motor 4 S80 Connector for four way valve coil 5 S90 Connector for thermistors outdoor temperature outdoor heat exchanger discharge pipe 6 U V W Connector for compressor 7 HL1 HN1 S Connector for terminal board 8 E E2 Connector for earth 9 HR1 HR2 Connector for reactor 10 LED A LED for service monitor green 11 FU1 FU2 Fuse 3 15 A 250 V 12 FU3 Fuse 30 A 250 V 13 J5 Jumper for improvem...

Page 30: ...t Board Connector Wiring Diagram SiENBE04 925_A 16 Printed Circuit Board Connector Wiring Diagram PCB Detail PCB 1 Control PCB HN1 HL1 E E2 S V1 FU1 LED A S80 S20 S90 S70 HR2 HR1 FU2 S40 J5 U V W 2P208173 1 V3 V4 FU3 ...

Page 31: ...nitor PCB 5 S70 Connector for fan motor 6 S80 Connector for four way valve coil 7 S90 Connector for thermistors outdoor temperature outdoor heat exchanger discharge pipe 8 AC1 AC2 Connector for terminal board power supply 9 E1 E2 Connector for earth 10 HR1 HR2 Connector for reactor 11 U V W Connector for compressor 12 FU1 Fuse 30 A 250 V 13 FU2 FU3 Fuse 3 15 A 250 V 14 V2 V3 V5 V6 V11 Varistor 1 S...

Page 32: ...ENBE04 925_A 18 Printed Circuit Board Connector Wiring Diagram PCB Detail PCB 1 Main PCB PCB 2 Service Monitor PCB V3 V11 AC1 FU2 E1 E2 HR1 HR2 FU3 W 2P169046 5 S40 S20 V U S70 S90 S51 S10 AC2 S101 V5 S80 V6 V2 FU1 S102 SW1 3P169059 1 LED A SW4 C S52 ...

Page 33: ...Inverter POWERFUL Operation 31 1 11 Other Functions 32 2 Function of Thermistor 33 3 Control Specification 34 3 1 Mode Hierarchy 34 3 2 Frequency Control 35 3 3 Controls at Mode Changing Start up 37 3 4 Discharge Pipe Temperature Control 39 3 5 Input Current Control 40 3 6 Freeze up Protection Control 41 3 7 Heating Peak cut Control 41 3 8 Outdoor Fan Control 42 3 9 Liquid Compression Protection F...

Page 34: ...pted by additional parameters in the following cases Frequency restrictions Initial settings Forced cooling operation Inverter Principle To regulate the capacity a frequency control is needed The inverter makes it possible to vary the rotation speed of the compressor The following table explains the conversion principle Target temperature Set temperature Room temperature Room thermistor temperatur...

Page 35: ...nce the set temperature is reached the energy saving operation enables to maintain the room temperature at low power Frequency Limits The following functions regulate the minimum and maximum frequency Forced Cooling Operation Refer to Forced operation mode on page 48 for detail Refrigerant circulation rate high high f low f freq variable Refrigerant circulation rate low high speed low speed R2812 ...

Page 36: ...the auto swing process for cooling dry heating and fan 3 D Airflow Alternative repetition of vertical and horizontal swing motions enables uniform air conditioning of the entire room This function is effective for starting the air conditioner When the horizontal swing and vertical swing are both set to auto mode the airflow becomes 3 D airflow and the horizontal swing and vertical swing motions ar...

Page 37: ...In automatic fan speed operation upper limit is at M tap in 30 minutes from the operation start Heating On heating mode the fan speed is regulated according to the indoor heat exchanger temperature and the difference between the room thermistor temperature and the target temperature Note 1 During POWERFUL operation fan rotates at H tap 50 rpm 2 Fan stops during defrost operation 3 In time of therm...

Page 38: ...temperature at start up and the target temperature is divided into two zones Then the unit operates in the dry mode with an appropriate capacity for each zone to maintain the temperature and humidity at a comfortable level Room thermistor temperature at start up Target temperature X Thermostat OFF point Y Thermostat ON point Z 24ºC or more Room thermistor temperature at start up X 2 5ºC X 0 5ºC or...

Page 39: ...tion value 1 The set temperature Ts determines the target temperature Tt Ts 18 30 C 2 The target temperature Tt is calculated as Tt Ts C where C is the correction value C 0 C 3 Thermostat ON OFF point and mode switching point are as follows Tr means the room thermistor temperature 1 Heating Cooling switching point Tr Tt 2 5 C 2 Cooling Heating switching point Tr Tt 2 5 C 3 Thermostat ON OFF point ...

Page 40: ...returns to the zone C after being in the zone A The system resumes from defrost control in any zones except A The operation turns on in any zones except A The monitoring time has passed while the temperature difference is in the zone B Cooling Dry 10 minutes Heating 10 seconds Cooling Dry Heating B A OFF OFF ON C Room thermistor temperature target temperature 1 5 C R12319 Cooling 0 5 C Dry 0 5 C C...

Page 41: ...r then automatically raises the target temperature slightly in the case of cooling or lowers it slightly in the case of heating This prevents excessive cooling in summer and excessive heating in winter to ensure comfortable sleeping conditions and also conserves electricity Cooling Heating R10870 TIMER operation NIGHT SET Mode ON Target temperature 0 5 C temperature shift Operation stops at the se...

Page 42: ...ONO button When this function is activated the maximum capacity also decreases The remote control can send the ECONO command when the unit is in COOL HEAT DRY or AUTO operation This function can only be set when the unit is running Pressing the ON OFF button on the remote control cancels the function This function and POWERFUL operation cannot be used at the same time The latest command has the pr...

Page 43: ...n the indoor unit carries out a sampling every 20 msec and if it detects 10 cycles of the wave in one second in total corresponding to 20 msec 10 200 msec and when the ON signal continues 3 sec it judges human is in the room as the motion signal is ON 2 area INTELLIGENT EYE sensor is divided into 2 areas and detects humans in each area Image of 2 area INTELLIGENT EYE 1 sec sampling 20 msec High Lo...

Page 44: ...hift the airflow direction to area B left side 2 Detection signal ON in area A Shift the airflow direction to area B left side 3 Detection signal ON in area B Shift the airflow direction to area A right side 4 Detection signal OFF in both area A and B No change When the detection signal is OFF for 20 minutes in both area A and B the unit starts energy saving operation Others For dry operation you ...

Page 45: ...20 minutes Ex POWERFUL operation in cooling mode Operation mode Fan speed Target temperature COOL H tap 50 rpm 18 C DRY Dry rotating speed 50 rpm Lowered by 2 5 C HEAT H tap 50 rpm 31 C FAN H tap 50 rpm AUTO Same as cooling heating in POWERFUL operation The target temperature is kept unchanged R7096 Target temp Fan 50 rpm 18 C H tap Set tap 20 minutes It should be the lower limit of cooling temper...

Page 46: ...tton for 5 to 9 seconds while the unit is not operating Refer to Forced operation mode on page 48 for detail Note When the ON OFF button is pressed for 10 seconds or more the forced operation is stopped 1 11 4 Titanium Apatite Photocatalytic Air Purifying Filter This filter combines the Air Purifying Filter and Titanium Apatite Photocatalytic Deodorizing Filter as a single highly effective filter ...

Page 47: ...rge pipe temperature used in place of the inner temperature of the compressor rises abnormally the operating frequency becomes lower or the operation halts 2 The discharge pipe thermistor is used for detecting disconnection of the discharge pipe thermistor C Indoor Heat Exchanger Thermistor 1 The indoor heat exchanger thermistor is used for controlling target discharge pipe temperature The system ...

Page 48: ... Detail There are following modes stop cooling includes drying heating include defrosting Note Unless specified otherwise an indoor dry operation command is regarded as cooling operation Air conditioner control mode Forced operating mode Forced cooling for Pump Down Operation Normal operating mode Cooling Heating Defrosting Stop mode except for cooling heating modes by indoor command Preheating op...

Page 49: ...n upper limit frequency among the frequency upper limits of the following functions Compressor protection input current discharge pipe temperature heating peak cut freeze up protection defrost 3 Determine lower limit frequency The maximum value is set as an lower limit frequency among the frequency lower limits of the following functions Four way valve operation compensation draft prevention press...

Page 50: ...ency does not change for more than a certain fixed time the frequency is adjusted according to the ΔD value When the ΔD value is small the frequency is lowered When the ΔD value is large the frequency is increased 3 Frequency management when other controls are functioning When frequency is drooping Frequency management is carried out only when the frequency droops For limiting lower limit Frequenc...

Page 51: ...operation in open phase stops RXL20G2V1B9 Outdoor temperature 7 C Control A Outdoor temperature 7 C Control B Control A ON condition Discharge pipe temperature 10 C OFF condition Discharge pipe temperature 12 C Radiation fin temperature 90 C Control B ON condition Discharge pipe temperature 20 C OFF condition Discharge pipe temperature 22 C Radiation fin temperature 90 C RXL35G2V1B Outdoor tempera...

Page 52: ...compressor for heating 2 When the operation mode changes to cooling from heating 3 When starting compressor for defrosting or resetting 4 When starting compressor for the first time after the reset with the power is ON 5 When starting compressor for heating next to the suspension of defrosting 6 When starting compressor next to the fault of switching over cooling heating Set the lower limit freque...

Page 53: ...om going up further Detail Zone Control Stop zone When the temperature reaches the stop zone the compressor stops Drooping zone The timer starts and the frequency is drooping Keep zone The upper limit of frequency is kept Up zone The upper limit of frequency is increased Reset zone The upper limit of frequency is canceled 20 class 25 class 35 class ºC 110 110 110 ºC 105 103 103 ºC 101 102 101 5 ºC...

Page 54: ...ncy 2 Hz After this the output frequency is pulled down by 2 Hz every second until it reaches the keep zone Keep zone The present maximum frequency goes on Reset zone Limit of the frequency is canceled RXL20 35G2V1B RXL20G2V1B9 Limitation of current drooping and stop value according to the outdoor temperature The current droops when outdoor temperature becomes higher than a certain level depending...

Page 55: ...etermines the frequency upper limit to prevent abnormal high pressure Detail R4561 Reset zone Indoor heat exchanger thermistor temperature Up zone Keep zone Drooping zone Stop zone 0 C 5 5 C 7 5 C 9 5 C 13 C Reference Zone Control Stop zone When the temperature reaches the stop zone the compressor stops Drooping zone The timer starts and the frequency is drooping Keep zone The upper limit of frequ...

Page 56: ...ion speed of the outdoor fan is reduced by the command of the indoor outdoor quiet operation 7 Fan control for POWERFUL operation The rotation speed of the outdoor fan is increased while the POWERFUL operation 8 Fan speed control for pressure difference upkeep The rotation speed of the outdoor fan is controlled for keeping the pressure difference while cooling with low outdoor temperature When the...

Page 57: ...ion The compressor operates for 6 minutes More than minutes of accumulated time pass since the start of the operation or ending the previous defrosting Conditions for Canceling Defrost The judgment is made with outdoor heat exchanger temperature 4 C 18 C 20 class 25 class 35 class minutes 28 30 44 Hz 76 48 55 Hz 86 70 90 seconds 50 60 60 seconds 60 120 120 seconds 600 650 460 seconds 60 30 30 puls...

Page 58: ...ntrol when the discharge pipe thermistor is disconnected Feedback Control 1 Discharge pipe temperature control Detail The followings are the examples of control which function in each mode by the electronic expansion valve control R2833 X X X X X X X X X X X X X X X Control when frequency changed Control for abnormally high discharge pipe temperature Operation pattern function X not function When ...

Page 59: ...ng if the discharge pipe temperature exceeds a certain value the electronic expansion valve opens and the refrigerant runs to the low pressure side This procedure lowers the discharge pipe temperature 3 11 6 Disconnection of the Discharge Pipe Thermistor Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe temperature with the condensation temperat...

Page 60: ...fied value in a certain time period the target discharge pipe temperature control is canceled and the target opening of the electronic expansion valve is changed according to the shift 3 11 8 Target Discharge Pipe Temperature Control The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger temperature and the electronic expansion valve opening is adjusted so tha...

Page 61: ...ion If the power consumption is below the specified value and the frequency is higher than the specified frequency it is regarded as refrigerant shortage The power consumption is small comparing with that in the normal operation when refrigerant is insufficient and refrigerant shortage is detected by checking a power consumption II Detecting by discharge pipe temperature If the discharge pipe temp...

Page 62: ...e outdoor unit is not abnormal and not in the 3 minute standby mode 2 The outdoor unit is not operating The forced operation is allowed when the above both conditions are met Start 1 Press the forced operation ON OFF button SW1 on the indoor unit for 5 seconds 2 Press the forced operation ON OFF button SW1 on the outdoor unit Command frequency RXL20G2V1B 68 Hz RXL20G2V1B9 58 Hz RXL25G2V1B 47 Hz RX...

Page 63: ...Operation Manual 51 2 1 Auto Dry Cool Heat Fan Operation 52 2 2 Adjusting the Airflow Direction 54 2 3 COMFORT AIRFLOW and INTELLIGENT EYE Operation 56 2 4 POWERFUL Operation 59 2 5 OUTDOOR UNIT QUIET Operation 60 2 6 ECONO Operation 61 2 7 TIMER Operation 62 2 8 WEEKLY TIMER Operation 64 ...

Page 64: ...ever method of using it In order to meet this expectation of the users giving sufficient explanations taking enough time can be said to reduce about 80 of the requests for servicing However good the installation work is and however good the functions are the customer may blame either the room air conditioner or its installation work because of improper handling The installation work and handing ov...

Page 65: ...nce to start operation Press once again to stop it 6 TEMPERATURE adjustment buttons It changes the temperature setting 7 MODE selector button It selects the operation mode AUTO DRY COOL HEAT FAN 8 QUIET button OUTDOOR UNIT QUIET operation 9 ECONO button ECONO operation 10 SWING button Horizontal blades flaps 11 SWING button Louvers vertical blades 12 COMFORT SENSOR button COMFORT AIRFLOW and INTEL...

Page 66: ...essing of the button advances the mode setting in sequence AUTO DRY COOL HEAT FAN 2 Press ON OFF button ON is displayed on the LCD The OPERATION lamp lights up To stop operation 3 Press ON OFF button again ON disappears from the LCD 4 Then OPERATION lamp goes off To change the temperature setting 5 Press TEMPERATURE adjustment button 1 5 2 3 4 DRY or FAN mode AUTO or COOL or HEAT mode The temperat...

Page 67: ...witches into defrosting operation to take away the frost During defrosting operation hot air does not flow out of indoor unit A pinging sound may be heard during defrosting operation which however does not mean that the air conditioner has failures Note on COOL operation This air conditioner cools the room by blowing the hot air in the room outside so if the outside temperature is high the perform...

Page 68: ...isplayed on the LCD and the flaps will begin to swing 2 When the flaps have reached the desired position press SWING button once more The flaps will stop moving disappears from the LCD To adjust the vertical blades louvers 3 Press SWING button is displayed on the LCD 4 When the louvers have reached the desired position press the SWING button once more The louvers will stop moving disappears from t...

Page 69: ...sional 3 D Airflow Using three dimensional airflow circulates cold air which tends to collected at the bottom of the room and hot air which tends to collect near the ceiling throughout the room preventing areas of cold and hot developing ATTENTION Always use a remote control to adjust the angles of the flaps and louvers If you attempt to move it forcibly with hand when it is swinging the mechanism...

Page 70: ...e the COMFORT SENSOR button is pressed a different setting option is displayed on the LCD To cancel operation 2 Press COMFORT SENSOR button Press the button to select Blank 1 2 Blank Display Operation mode Explanation COMFORT AIRFLOW INTELLIGENT EYE Blank No function COMFORT AIRFLOW and INTELLIGENT EYE The flaps will adjust the airflow direction upward while cooling and adjust the airflow directio...

Page 71: ...djustments The flaps will move upward while cooling so that the airflow will be directed upward The flaps will move downward while heating so that the airflow will be directed downward Cooling operation Heating operation The INTELLIGENT EYE sensor according to the following situations Area 1 Area 2 Area 1 Area 2 Area 1 Area 2 A person is detected in area 1 A person is detected in area 2 The air co...

Page 72: ...E functions simultaneously When both of them are in use the air conditioner will not direct the airflow towards the people Sensor may not detect moving objects further than 5m away Check the application range Sensor detection sensitivity changes according to indoor unit location the speed of passersby temperature range etc The sensor also mistakenly detects pets sunlight fluttering curtains and li...

Page 73: ...ation cannot be used together with ECONO QUIET or COMFORT Operation Priority is given to the function of whichever button is pressed last POWERFUL Operation can only be set when the unit is running Pressing the operation stop button causes the settings to be canceled and the disappears from the LCD POWERFUL operation will not increase the capacity of the air conditioner if the air conditioner is a...

Page 74: ...d on the LCD To cancel OUTDOOR UNIT QUIET operation 2 Press QUIET button again disappears from the LCD Notes on COMFORT AIRFLOW operation This function is available in COOL HEAT and AUTO modes This is not available in FAN and DRY mode POWERFUL operation and OUTDOOR UNIT QUIET operation cannot be used at the same time Priority is given to the function of whichever button is pressed last OUTDOOR UNI...

Page 75: ...CONO mode vary with the connecting outdoor unit Notes on ECONO operation ECONO Operation can only be set when the unit is running Pressing the OFF button causes the setting to be canceled and the disappears from the LCD ECONO operation is a function which enables efficient operation by limiting the power consumption of the outdoor unit operating frequency ECONO operation functions in AUTO COOL DRY...

Page 76: ...ting by 10 minutes Holding down either button changes the setting rapidly 3 Press OFF TIMER button again The TIMER lamp lights up To cancel the OFF TIMER operation 4 Press CANCEL button The TIMER lamp goes off When TIMER is set the present time is not displayed Once you set ON OFF TIMER the time setting is kept in the memory The memory is canceled when remote control batteries are replaced When op...

Page 77: ...me setting by 10 minutes Holding down either button changes the setting rapidly 3 Press ON TIMER button again The TIMER lamp lights up To cancel the ON TIMER operation 4 Press CANCEL button The TIMER lamp goes off To combine ON TIMER and OFF TIMER A sample setting for combining the two timers is shown below In the following cases set the timer again After a breaker has turned OFF After a power fai...

Page 78: ...ttings for example makes it possible to schedule operating mode and set temperature changes Furthermore by using OFF OFF OFF OFF settings only the turn OFF time of each day can be set This will turn OFF the air conditioner automatically if the user forgets to turn it OFF 6 00 8 30 17 30 22 00 25 C 27 C 6 00 8 30 17 30 22 00 25 C 27 C 8 00 10 00 19 00 21 00 27 C 27 C 25 C 27 C 27 C 25 C 25 C Make t...

Page 79: ...select the desired mode Pressing the SELECT button changes ON or OFF setting in sequence In case the reservation has already been set selecting blank deletes the reservation Go to STEP 9 if blank is selected 5 Press NEXT button The ON OFF TIMER mode will be set and the time blink 6 Press SELECT button to select the desired time The time can be set between 0 00 and 23 50 in 10 minute intervals To r...

Page 80: ...he week Refer to Copy mode Notes on WEEKLY TIMER operation Do not forget to set the clock on the remote control first The day of the week ON OFF TIMER mode time and set temperature only for ON TIMER mode can be set with WEEKLY TIMER Other settings for ON TIMER are based on the settings just before the operation Both WEEKLY TIMER and ON OFF TIMER operation cannot be used at the same time The ON OFF...

Page 81: ... of the week 5 Press COPY button The reservation will be copied to the selected day of the week The whole reservation of the selected day of the week will be copied To continue copying the settings to other days of the week repeat STEP 4 and STEP 5 6 Press button to complete the setting is displayed on the LCD and WEEKLY TIMER operation is activated 6 00 8 30 17 30 22 00 25 C 27 C Monday COPY Prog...

Page 82: ...rmed 1 Press button The day of the week and the reservation number of the current day will be displayed 2 Press SELECT button to select the day of the week and the reservation number to be confirmed Pressing the SELECT button displays the reservation details To change the confirmed reserved settings select the reservation number and press NEXT button The mode is switched to setting mode Go to Sett...

Page 83: ...r to Setting mode When selecting desired mode at STEP 4 in setting mode select blank The reservation will be deleted The reservations for each day of the week This function can be used for deleting reservations for each day of the week 5 Press button 6 Select the day of the week to be canceled with the SELECT button 7 Hold the WEEKLY button for 5 seconds The selcted reservation will be canceled Al...

Page 84: ...nit PCB Abnormality 84 4 9 OL Activation Compressor Overload 86 4 10 Compressor Lock 87 4 11 DC Fan Lock 88 4 12 Input Overcurrent Detection 89 4 13 Four Way Valve Abnormality 90 4 14 Discharge Pipe Temperature Control 92 4 15 High Pressure Control in Cooling 94 4 16 Compressor System Sensor Abnormality 96 4 17 Position Sensor Abnormality 98 4 18 DC Voltage Current Sensor Abnormality 20 25 Class 1...

Page 85: ...protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions 2 When a signal transmission error occurs between the indoor and outdoor units In either case conduct the diagnostic procedure described in the following pages Outdoor Unit The outdoor unit has one green LED LED A on the PCB When the LED A blinks the microcomputer works in order R12187 Operation lamp g...

Page 86: ...ating operation cannot be used when the outdoor temperature is 20 C or higher and cooling operation cannot be used when the outdoor temperature is below 10 C Diagnose with remote control indication 75 The unit operates but does not cool or does not heat Check for wiring and piping errors in the connection between the indoor and outdoor units Conduct the wiring piping error check described on the p...

Page 87: ...equence shown below Note 1 A short beep pi and two consecutive beeps pi pi indicate non corresponding codes 2 To return to the normal mode hold the timer cancel button down for 5 seconds When the remote control is left untouched for 60 seconds it also returns to the normal mode No Code No Code No Code 1 00 13 C7 25 UA 2 U4 14 A3 26 UH 3 L5 15 H8 27 P4 4 E6 16 H9 28 L3 5 H6 17 C9 29 L4 6 H0 18 C4 3...

Page 88: ... the figure until you hear the sound of beep or pi pi 3 Diagnose by the sound H pi The figure of the ten s place does not accord with the error code H pi pi The figure of the ten s place accords with the error code but the one s not H beep The both figures of the ten s and one s place accord with the error code See 7 4 Press the MODE button The figure of the one s place blinks R8381 R8382 R8383 R8...

Page 89: ...eep The both figures of the ten s and one s place accord with the error code 7 Determine the error code The figures indicated when you hear the beep sound are error code Error codes and description Refer to page 75 8 Press the MODE button to exit from the diagnosis mode The display means the trial operation mode Refer to page 267 for trial operation 9 Press the ON OFF button twice to return to the...

Page 90: ...bnormality 81 Outdoor Unit E1 Outdoor unit PCB abnormality 84 E5H OL activation compressor overload 86 E6H Compressor lock 87 E7 DC fan lock 88 E8 Input overcurrent detection 89 EA Four way valve abnormality 90 F3 Discharge pipe temperature control 92 F6 High pressure control in cooling 94 H0 Compressor system sensor abnormality 96 H6 Position sensor abnormality 98 H8 DC voltage current sensor abn...

Page 91: ...ion of connector Troubleshooting Note Check the following connector Check the combination of the indoor and outdoor unit OK Check the connection of connectors See Note Correct the connection OK Error repeats YES NO NO YES NO YES R11704 Caution To secure the connection once disconnect the connector and then reconnect it Match the compatible models Replace the indoor unit PCB 1 Replace the indoor un...

Page 92: ...ring heating operation the temperature detected by the indoor heat exchanger thermistor is used for the heating peak cut control operation halt outdoor fan stop etc Malfunction Decision Conditions Freeze up protection control During cooling operation the indoor heat exchanger temperature is below 0 C Heating peak cut control During heating operation the indoor heat exchanger temperature is above 6...

Page 93: ...lean the air filter Clean the indoor heat exchanger Replace the indoor unit PCB Replace the thermistor Does it conform to the thermistor characteristic chart Check the air filter Check the dust accumulation on the indoor heat exchanger Is there any short circuit Is it very dirty Is it very dirty Check the air passage Be sure to turn off the power switch before connecting or disconnecting connector...

Page 94: ... is used to determine abnormal fan motor operation Malfunction Decision Conditions The detected rotation speed does not reach the demanded rotation speed of the target tap and is less than 50 of the maximum fan motor rotation speed Supposed Causes Layer short inside the fan motor winding Breaking of wire inside the fan motor Breaking of the fan motor lead wires Defective capacitor of the fan motor...

Page 95: ...he fan rotate smoothly Does the fan rotate Is the motor power supply voltage 310 340 VDC generated Is the motor control voltage 15 VDC generated Turn off the power supply and rotate the fan by hand Turn the power on and start operation Be sure to turn off the power switch before connecting or disconnecting connectors or parts may be damaged Check No 01 Check the output of the fan motor connector R...

Page 96: ...ompressor operation Supposed Causes Disconnection of connector Defective thermistor Defective indoor unit PCB Troubleshooting Check No 06 Refer to P 120 C4 Indoor heat exchanger thermistor C9 Room temperature thermistor YES R7134 NO Check No 06 Check the thermistor resistance value YES NO Caution Correct the connection Replace the thermistor Replace the indoor unit PCB Is it normal Is it normal Ch...

Page 97: ...supply waveform Check the voltage of the connection wires on the indoor terminal board between No 1 and No 3 and between No 2 and No 3 YES YES Replace the indoor unit PCB Locate the cause of the disturbance of the power supply waveform and correct it NO R12160 NO YES YES NO NO Caution Correct the indoor unit outdoor unit connection wires Diagnose the outdoor unit PCB Before you check the LED A can...

Page 98: ...wiring of connecting wires Wrong indoor unit PCB or outdoor unit PCB mounted Defective indoor unit PCB Defective outdoor unit PCB Troubleshooting R11707 Caution NO YES YES YES NO NO Check the code numbers 2P01234 for example of the indoor and outdoor unit PCB with the Parts List Match the compatible models Change for the correct PCB Replace the indoor unit PCB or the outdoor unit PCB OK Matched co...

Page 99: ...CBs Noise Momentary fall of voltage Momentary power failure etc Troubleshooting 20 35 class Caution Be sure to turn off the power switch before connecting or disconnecting connectors or parts may be damaged NO YES YES R12161 YES NO NO Replace the outdoor unit PCB Ground the system Zero cross signal abnormality Replace the outdoor unit PCB 1 Replace the harness Check to see if the outdoor unit is g...

Page 100: ...ty Replace the outdoor unit PCB Replace the harness Check to see if the outdoor unit is grounded Is LED A blinking Grounded NO Replace the connecting wires between the indoor and outdoor units Check the voltage between No 1 and No 2 on the outdoor terminal board Is it normal Is the harness broken Turn on the power again Before you check the LED A cancel the standby electricity saving function by o...

Page 101: ...ctive stop valve Troubleshooting Check No 04 Refer to P 118 Check No 05 Refer to P 119 Check No 06 Refer to P 120 Check No 11 Refer to P 122 R11999 Caution YES NG Discharge pipe thermistor NO OK OK NG Refrigerant shortage Water mixed Stop valve NG OK NG OK Insert the thermistor in position Replace the discharge pipe thermistor Replace the electronic expansion valve or the coil Refer to the refrige...

Page 102: ...for about 5 minutes without any other error Supposed Causes Compressor locked Compressor harness disconnected Troubleshooting Turn off the power Disconnect the harnesses U V and W R8399 Caution NO YES YES NO NO YES Check with the inverter checker Turn off the power and reconnect the harnesses Turn on the power again and restart the system Precaution before turning on the power again Make sure the ...

Page 103: ...her error Supposed Causes Disconnection of the fan motor Foreign matters stuck in the fan Defective fan motor Defective outdoor unit PCB Troubleshooting Check No 15 Refer to P 124 R11708 Caution YES YES NO YES NO NO YES NO Turn on the power Rotate the fan Check No 15 Check the rotation pulse input on the outdoor unit PCB Turn off the power and reconnect the connector Remove them Replace the outdoo...

Page 104: ...e power switch before connecting or disconnecting connectors or parts may be damaged An input overcurrent may result from wrong internal wiring If the wires have been disconnected and reconnected for part replacement for example and the system is interrupted by an input overcurrent take the following procedure R11709 NO YES YES NO Start operation and measure the input current Check No 08 Check the...

Page 105: ...ditions A following condition continues over 1 10 minutes depending on the model after operating for 5 10 minutes depending on the model Cooling Dry room thermistor temp indoor heat exchanger temp 5 C Heating indoor heat exchanger temp room thermistor temp 5 C If the error repeats the system is shut down Reset condition Continuous run for about 60 minutes without any other error Supposed Causes Di...

Page 106: ...r way valve defective or dust clogged Reconnect in position Caution Be sure to turn off the power switch before connecting or disconnecting connectors or parts may be damaged R11710 Four way valve coil disconnected loose Harness out of connector Any thermistor disconnected Check No 06 Check the thermistors Check No 11 Check the refrigerant line Check No 05 Check the four way valve switching output...

Page 107: ...ts the system is shut down Reset condition Continuous run for about 60 minutes without any other error Supposed Causes Defective discharge pipe thermistor Defective outdoor heat exchanger thermistor or outdoor temperature thermistor Defective electronic expansion valve or coil Refrigerant shortage Defective four way valve Water mixed in refrigerant Defective stop valve Defective outdoor unit PCB S...

Page 108: ...efrigerant shortage Four way valve Water mixed Stop valve OK OK OK NG NG Check No 06 Check the thermistors Check No 11 Check the refrigerant line Check No 04 Check the electronic expansion valve Replace the defective thermistor Replace the electronic expansion valve or the coil Refer to the refrigerant line check procedure Replace the outdoor unit PCB Be sure to turn off the power switch before co...

Page 109: ...xceeds the limit Malfunction Decision Conditions The temperature sensed by the outdoor heat exchanger thermistor rises above C The error is cleared when the temperature drops below C Supposed Causes The installation space is not large enough Dirty outdoor heat exchanger Defective outdoor fan motor Defective stop valve Defective electronic expansion valve or coil Defective outdoor heat exchanger th...

Page 110: ...e outdoor unit PCB Replace the electronic expansion valve or the coil Replace the outdoor unit PCB Clean the outdoor heat exchanger Change the installation location or direction Check the installation space NG OK OK NG NG OK OK OK NG NG Check No 09 Check the outdoor fan Check No 08 Check the discharge pressure Check No 04 Check the electronic expansion valve Check No 06 Check the outdoor heat exch...

Page 111: ... output converted to voltage value The DC voltage before compressor start up is below 50 V Supposed Causes Broken or disconnection of harness Defective outdoor unit PCB Troubleshooting Caution Be sure to turn off the power switch before connecting or disconnecting connectors or parts may be damaged NO R11712 YES Turn off the power and turn it on again YES NO Replace the harness No problem Keep on ...

Page 112: ...O YES Connect it properly NO YES Replace the reactor NO YES Replace the compressor or the compressor relay harness Restart the operation again and if the error occurs again replace the outdoor unit PCB NO YES Disconnect the reactor from the outdoor unit PCB and measure the resistance value between reactor terminals with tester Disconnect the compressor relay harness from the outdoor unit PCB and m...

Page 113: ...ng condition through the position detection circuit Malfunction Decision Conditions If the error repeats the system is shut down Reset condition Continuous run for about 11 minutes 35 class 5 minutes without any other error Supposed Causes Disconnection of the compressor relay cable Defective compressor Defective outdoor unit PCB Start up failure caused by the closed stop valve Input voltage is ou...

Page 114: ...80 NO NO NO YES YES NO YES YES Check No 29 Check the short circuit of the diode bridge Check with the inverter checker Turn off the power Disconnect the harnesses U V and W Turn on the power Check the electrolytic capacitor voltage Electrical components or compressor harnesses connected as specified Replace the outdoor unit PCB Replace the compressor Correct the power supply or replace the outdoor...

Page 115: ...rrect the power supply Voltage as rated R11471 NO NO YES NO YES YES Check with the inverter checker Turn off the power Disconnect the harnesses U V and W Turn on the power Check the electrolytic capacitor voltage Electrical components or compressor harnesses connected as specified Replace the outdoor unit PCB Replace the compressor Correct the power supply or replace the outdoor unit PCB Reconnect...

Page 116: ...unning frequency and the input current Malfunction Decision Conditions The compressor running frequency is above 52 Hz If the error repeats 4 times the system is shut down Reset condition Continuous run for about 60 minutes without any other error Supposed Causes Defective outdoor unit PCB Troubleshooting Replace the outdoor unit PCB Caution Be sure to turn off the power switch before connecting o...

Page 117: ...ning frequency and CT detected input current Malfunction Decision Conditions The compressor running frequency is more than 55 Hz and the CT input current is below 0 5 A If the error repeats 4 times the system is shut down Reset condition Continuous run for about 60 minutes without any other error Supposed Causes Defective power module Breakage of wiring or disconnection Defective reactor Defective...

Page 118: ... on the power again and restart operation Compressor running 320 50 VDC Any LED OFF Running current as shown at right with relay cable 1 or 2 Voltage within the allowable range Supply voltage 15 Replace the outdoor unit PCB Replace the outdoor unit PCB Replace the outdoor unit PCB Check the supply voltage Replace the compressor Capacitor charged when the indoor unit or outdoor unit main relay turn...

Page 119: ... V 25 class 0 02 V with the power on J3 error is judged if the discharge pipe temperature is lower than the heat exchanger temperature Supposed Causes Disconnection of the connector for the thermistor Defective thermistor Defective heat exchanger thermistor in the case of J3 error outdoor heat exchanger thermistor in cooling operation or indoor heat exchanger thermistor in heating operation Defect...

Page 120: ...he following thermistors Outdoor temperature thermistor Discharge pipe thermistor Outdoor heat exchanger thermistor Cooling Outdoor heat exchanger temperature Heating Indoor heat exchanger temperature Replace the indoor heat exchanger thermistor Replace the outdoor unit PCB Replace the indoor unit PCB Error displayed again on remote control Indoor heat exchanger thermistor functioning Check No 06 ...

Page 121: ...he compressor off the radiation fin temperature is above C The error is cleared when the radiation fin temperature drops below C To cool the electrical components the outdoor fan starts when the radiation fin temperature rises above C and stops when it drops below C Supposed Causes Defective outdoor fan motor Short circuit Defective radiation fin thermistor Disconnection of connector Defective out...

Page 122: ...urn it on again Check the radiation fin temperature Check No 07 Check the installation condition Radiation fin dirty Above C Check No 09 Check the outdoor fan or related Error again or outdoor fan activated Replace the outdoor unit PCB Replace the outdoor unit PCB Replace the fan motor Correct the connectors and fan motor lead wire Clean up the radiation fin Be sure to turn off the power switch be...

Page 123: ...mpressor on is above C The error is cleared when the radiation fin temperature drops below C If the error repeats the system is shut down Reset condition Continuous run for about 60 minutes without any other error Supposed Causes Defective outdoor fan motor Short circuit Defective radiation fin thermistor Disconnection of connector Defective outdoor unit PCB Silicon grease is not applied properly ...

Page 124: ...dirty Check No 09 Check the outdoor unit fan or related Error displayed again Has PCB been replaced Check if the silicon grease applied properly on the radiation fin If not apply it See Note Check the power transistor and the radiation fin for looseness If they are found to be fit tightly replace the outdoor unit PCB or the power transistor Replace the outdoor unit PCB Replace the fan motor Correc...

Page 125: ...while the compressor is running A speed error occurs while the compressor is running An output overcurrent signal is fed from the output overcurrent detection circuit to the microcomputer If the error repeats the system is shut down Reset condition Continuous run for about 11 minutes 35 class 5 minutes without any other error Supposed Causes Poor installation condition Closed stop valve Defective ...

Page 126: ...eck No 07 Check the installation condition Check with the inverter checker Turn off the power and disconnect the harnesses U V and W Turn off the power and reconnect the harnesses Turn on the power again and start operation Turn off the power and turn it on again to start the system See if the same error occurs Check the supply voltage Keep on using as it is Check the connectors and other componen...

Page 127: ...erature tends to rise Refrigerant shortage detection III Refrigerant shortage is detected by checking the difference between suction and discharge temperature Malfunction Decision Conditions Refrigerant shortage detection I The following conditions continue for 7 minutes 20 25 class Input current input voltage output frequency Output frequency 35 class Input current output frequency Output frequen...

Page 128: ...ses Disconnection of the discharge pipe thermistor indoor or outdoor heat exchanger thermistor room or outdoor temperature thermistor Closed stop valve Refrigerant shortage refrigerant leakage Poor compression performance of compressor Defective electronic expansion valve C Cooling room thermistor temperature indoor heat exchanger temperature 4 0 outdoor heat exchanger temperature outdoor temperat...

Page 129: ...he pipe flare or replace the union Check the power transistor harness for looseness Correct it as required Also replace the cracked pipe Check the pipes for improper contact Correct them as required Also replace the cracked pipe Replace the electronic expansion valve Replace the defective one s Completed Refrigerant shortage error again Oil oozing at internal piping Stop valve closed Compressor vi...

Page 130: ...voltage detection The voltage detected by the DC voltage detection circuit is below 150 180 V depending on the model Over voltage detection An over voltage signal is fed from the over voltage detection circuit to the microcomputer The voltage is over 400 V If the error repeats the system is shut down Reset condition Continuous run for about 11 minutes 35 class 5 minutes without any other error Sup...

Page 131: ...h before connecting or disconnecting connectors or parts may be damaged NO YES YES NO YES Precaution before turning on the power again NO Replace the fan motor or the outdoor unit PCB Check the supply voltage Rotate the fan by hand Disturbance factors Noise Power supply distortion Repeat a few times Make sure the power has been off for at least 30 seconds Turn on the power again System restarted D...

Page 132: ...when the data sent from the PM1 can not be received for 9 seconds The error counter is reset when the data from the PM1 can be successfully received Supposed Causes Defective outdoor unit PCB Troubleshooting R7185 Caution NO YES Turn off the power and turn it on again Error again Replace the outdoor unit PCB Observe the operating condition in long term The cause can be an external factor other tha...

Page 133: ...ower off and on again and check to see if the EV generate latching sound 3 If the EV does not generate latching sound in the above step 2 disconnect the connector and check the continuity using a tester 4 Check the continuity between the pins 1 6 and 3 6 and between the pins 2 5 and 4 5 If there is no continuity between the pins the EV coil is faulty 5 If the continuity is confirmed in the above s...

Page 134: ...e coil from the connector and check the continuity Start heating operation Four way valve coil Cooling Dry No continuity Heating Continuity Replace the outdoor unit PCB Replace the four way valve coil Replace the four way valve Four way valve coil resistance at 1000 2000 Ω S80 voltage at 220 240 VAC with compressor on Fig 1 R11904 Fig 1 Voltage at S80 220 240 VAC Time Compressor ON ...

Page 135: ... temperature and resistance is shown in the table and the graph below For the models in which the thermistor is directly mounted on the PCB disconnect the connector for the PCB and measure Thermistor R25 C 20 kΩ B 3950 Temperature C 20 211 0 kΩ 15 150 0 10 116 5 5 88 0 0 67 2 5 51 9 10 40 0 15 31 8 20 25 0 25 20 0 30 16 0 35 13 0 40 10 6 45 8 7 50 7 2 Tester Resistance range R11906 kΩ 150 100 50 1...

Page 136: ...he outdoor heat exchanger very dirty Change the installation location or direction Change the installation location or direction Clean the outdoor heat exchanger Change the installation location or direction Check the outdoor temperature The outdoor temperature should be 46 C or lower R11718 Not dirty YES YES Dirty NO NO NO YES Is the air filter or indoor outdoor heat exchanger dirty Is the connec...

Page 137: ...form disturbance near the zero cross sections circled in Fig 2 5 1 9 Inverter Units Refrigerant System Check Check No 11 R7159 YES YES NO NO Outdoor fan system is functioning Check the outdoor fan system Go to Check No 15 Outdoor fan running Fan motor lead wire connector disconnected Reconnect the connector Fig 1 Fig 2 Refrigerant system check Check for refrigerant leakage See the service diagnosi...

Page 138: ... from the outdoor unit PCB To disengage the connector press the protrusion on the connector Follow the procedure below to measure resistance between the terminals of the DB1 and the terminals of the compressor with a multi tester Evaluate the measurement results for a judgment OL lead wire Thermistor lead wire Fan motor lead wire Compressor lead wire Reactor lead wire Four way valve lead wire Elec...

Page 139: ...an motor is rotated 1 turn by hand When the fuse is melted check the outdoor fan motor for proper function If NG in step 2 Defective PCB Replace the outdoor unit PCB If NG in step 4 Defective Hall IC Replace the outdoor fan motor If OK in both steps 2 and 4 Replace the outdoor unit PCB RXL20G2V1B9 1 Check that the voltage between the pins 10 11 is 15 VDC 2 Check if the Hall IC generates the rotati...

Page 140: ...sistance between the pins of the DB1 as below If the resistance is or less than 1 kΩ short circuit occurs on the main circuit 20 class 25 class terminal of the tester in case of digital terminal 2 3 4 2 3 1 terminal of the tester in case of digital terminal 4 2 3 1 2 3 Resistance in OK several kΩ several MΩ several kΩ several MΩ Resistance in NG 0 Ω or 0 0 0 Ω or R12035 Tester 1 2 3 4 R12266 Teste...

Page 141: ... 178 2 9 Removal of Compressor 181 3 Outdoor Unit RXL20G2V1B9 183 3 1 Removal of Outer Panels Fan Motor 183 3 2 Removal of Electrical Box 192 3 3 Removal of Drain Pan Heater 195 3 4 Removal of PCB 197 3 5 Removal of Reactor Partition Plate 205 3 6 Removal of Sound Blanket 207 3 7 Removal of Four Way Valve 209 3 8 Removal of Compressor 212 4 Outdoor Unit RXL25G2V1B 214 4 1 Removal of Outer Panels 2...

Page 142: ...SiENBE04 925_A Removal Procedure 127 5 6 Removal of Sound Blanket Thermistors 259 5 7 Removal of Four Way Valve 261 5 8 Removal of Electronic Expansion Valve 262 5 9 Removal of Compressor 263 ...

Page 143: ... pressed for 5 seconds the forced cooling operation is performed for about 15 minutes 2 Remove the air filter 1 Hold the both sides of the front panel and open the panel to the position where it stops 2 Slightly push up the center knob of the air filter and release the hooks The air filter is not marked for difference between the right and left sides The air filter can be set easily by inserting i...

Page 144: ...urifying filter is not marked for difference between the right and left sides 2 Remove the Titanium apatite photocatalytic air purifying filter ASSY by bending the air filter and unfastening the projections from the air filter frame 3 Remove the Titanium apatite photocatalytic air purifying filter from its frame at 5 positions by bending it Step Procedure Points R7904 Air filter Titanium apatite p...

Page 145: ...er supplies before disassembling work Step Procedure Points 1 Hold the both sides of the front panel and open the panel over the position where it stops 2 Slide the left rotary shaft to the right and release it 3 Slide the right rotary shaft to the left and release it 4 Remove the front panel R7906 Front panel R7907 Rotary shaft R7909 Rotary shaft R7910 ...

Page 146: ...he front panel make sure that the shaft is fitted in the guide before closing the panel Caution on Mounting When mounting the front panel fit the right and left rotary shafts one by one into the grooves and fully push them in position Step Procedure Points R7908 Shaft ...

Page 147: ...er supplies before disassembling work Step Procedure Points 1 Remove the service cover 1 Remove the screw of the service cover Preparation Remove the front panel according to the Removal of Front Panel 2 Pull out the service cover diagonally down in the direction of the arrow 3 The figure shows the appearance of the inside R7911 Service cover R8077 R7913 ...

Page 148: ...e 133 2 Remove the front grille 1 Remove the 2 screws one each at the right and left 2 The front grille has 3 hooks at the top 3 Unfasten the left hook 4 Unfasten the center hook Step Procedure Points R12267 R8076 Hooks R7917 Front grille R7918 ...

Page 149: ... the right hook 6 Pull the upper part of the front grille out and lift the lower part up and then remove the front grille Caution on Mounting When mounting the front grille make sure that the 3 hooks are fastened as they were Step Procedure Points R8078 R12268 ...

Page 150: ...to the upper side and the small horizontal blade to the lower side Do not put them in the wrong place 2 Unfasten the center shaft while bending the horizontal blade large slightly 3 Unfasten the left shaft 4 Unfasten the key alignment shaft at the right side Caution on Mounting There is a key alignment at the right shaft When mounting insert the right shaft first while turning After inserting the ...

Page 151: ...ding the horizontal blade small slightly 2 Unfasten the left shaft 3 Unfasten the key alignment shaft at the right side 3 Remove the fan guard 1 Unfasten the hooks at the lower part of the fan guard with a flat screwdriver 2 Remove the fan guard Step Procedure Points R7925 Horizontal blade small R7926 R7927 Key R7928 R8079 ...

Page 152: ...lock rod 3 Unfasten the hooks at the upper 3 positions by pressing them with a flat screwdriver 4 Remove the vertical blade ASSY A vertical blade ASSY has 5 fins It is impossible to replace only one fin The vertical blade ASSY is not marked for difference between right and left Step Procedure Points R12270 Vertical blade ASSY Pivot Interlock shaft R10302 Interlock rod R10303 R12269 Hook ...

Page 153: ...tep Procedure Points 1 The figure shows the connections of wire harnesses Preparation Remove the front grille according to the Removal of Front Grille 2 Remove the screw of the wire fixture 3 Remove the screws on the terminal board to disconnect the connecting wires 4 Disconnect the connector for fan motor S1 R7931 Electrical box R7932 Wire fixture R7933 Terminal board Connecting wires R7934 S1 ...

Page 154: ... Release the harness for swing motors from the hook 7 Pull out the indoor heat exchanger thermistor Be careful not to lose the clip of the thermistor 8 Remove the screw and detach the earth wire Step Procedure Points R7935 S41 R7936 R7937 Indoor heat exchanger thermistor Clip R11268 R7938 Earth wire ...

Page 155: ...k at the upper far side by pressing it from above and pulling the electrical box toward yourself 11 Lift up the electrical box and pull it out There is a hook also at the lower part of the back When mounting the electrical box make sure that it is securely fastened Step Procedure Points R3939 R8081 Hook R8082 ...

Page 156: ...ration Remove the electrical box according to the Removal of Electrical Box 2 Unfasten the hooks at the upper 2 positions of the shield plate 3 Unfasten the hook at the side of the shield plate 4 Lift up the shield plate to unfasten the lower hooks and remove it 2 Remove the terminal board 1 Remove the screw to remove the terminal board R8083 Signal receiver PCB Control PCB Shield plate INTELLIGEN...

Page 157: ...ve the signal receiver unit 1 Unfasten the 3 hooks 2 Unfasten the hook on the opposite side and lift up the signal receiver unit 3 Remove the signal receiver unit Step Procedure Points R12277 Signal receiver unit R8262 R12278 Hook R8088 Signal receiver unit ...

Page 158: ...ENT EYE sensor PCB 2 Disconnect the connector S26 from the INTELLIGENT EYE sensor PCB 5 Remove the signal receiver PCB 1 Unfasten the 3 hooks and remove the signal receiver PCB 2 Disconnect the connector S48 from the signal receiver PCB Step Procedure Points R8092 INTELLIGENT EYE sensor PCB R8093 S26 R8090 Signal receiver PCB R8091 S48 ...

Page 159: ...gure shows the connection of wire harness for the display PCB 2 Unfasten the 4 hooks and remove the display PCB 3 Disconnect the connector S49 from the display PCB 7 Remove the control PCB 1 Unfasten the lower 2 hooks of the control PCB Step Procedure Points R8094 Display PCB R10318 Hook R8096 LED 3 Green LED 1 Green S49 LED 2 Yellow R8097 Hook Control PCB ...

Page 160: ...figures show the names of the PCB component parts S1 DC fan motor S21 HA connector S25 INTELLIGENT EYE sensor PCB S26 control PCB S32 indoor heat exchanger thermistor S41 swing motors S46 display PCB S47 signal receiver PCB S48 S49 control PCB Refer to page 9 10 for detail Step Procedure Points R8098 R8099 S32 S1 S21 S47 S25 S46 S41 R8100 S48 S49 S26 LED3 Green LED1 Green LED2 Yellow ...

Page 161: ... air may be sucked in to generate an over pressure in refrigeration cycle thus resulting in pipe rupture or accidental injury 3 Lift up the indoor unit slightly and pull out the drain hose The illustration is for the case of left piping Place a plastic sheet under the drain pan to prevent from wetting the floor with remaining drain If the drain hose is embedded in the wall disconnect the drain hos...

Page 162: ... out the pipe 2 Widen the auxiliary pipe by about 10 20 degrees Caution When dismounting or mounting the indoor heat exchanger be sure to wear gloves or wrap it with cloth before proceeding You may be injured by the fins 3 Remove the 2 screws on the left side 4 Unfasten the lower hook on the right side with a flat screwdriver Step Procedure Points R10622 Piping fixture R10543 Unbending angle 10 20...

Page 163: ...unfastening the lower hooks lift up the indoor heat exchanger by its right side When mounting the indoor heat exchanger make sure that the hook right is fastened 6 Remove the indoor heat exchanger Step Procedure Points R1032 Indoor heat exchanger Hook R10328 ...

Page 164: ... before disassembling work Step Procedure Points 1 Remove the swing motor for vertical blade 1 Lift the indoor unit with a wooden base 2 Remove the screw behind the drain hose and disconnect the drain hose 3 Remove the screw at the rear and remove the screws on the right and the left side of the swing motors R10323 R10329 Drain hose R10330 Swing motors ...

Page 165: ...screwdriver 5 Remove the swing motor unit 6 Detach the interlock shaft from the swing motor with a flat screw driver 7 Remove the vertical blade interlock with a flat screwdriver Step Procedure Points R12270 Vertical blade ASSY Pivot Interlock shaft R8126 Swing motor unit R8127 Interlock shaft R10331 Vertical blade interlock ...

Page 166: ...NBE04 925_A Indoor Unit Removal Procedure 151 8 Remove the 2 screws 9 Remove the swing motor for vertical blade 10 Disconnect the connector Connector green Step Procedure Points R10332 Screws R10333 R10334 ...

Page 167: ...pposite the horizontal blades do not move smoothly or the noise may be heard 1 Set the motor for the upper blade first connector white 2 Then set the motor for the lower blade connector red 3 Fix the both motors with a screw 1 Remove the screw and remove the swing motors for horizontal blades 2 Disconnect the harnesses from the motors Step Procedure Points R8131 Connector for lower blade red Conne...

Page 168: ...t least 10 min before disassembling work Step Procedure Points 1 Remove the right side panel Preparation Remove the indoor heat exchanger according to the Removal of Indoor Heat Exchanger 1 Remove the 2 screws and remove the right side panel 2 Release the fan motor wire harness from the hook R8112 R8113 Right side panel R8114 R8115 ...

Page 169: ...2 screws of the fan motor fixing plate 4 Unfasten the hook of the fan motor fixing plate and remove the plate 2 Remove the fan rotor 1 Dislocate the fan rotor by sliding it to the right Step Procedure Points R8116 Fan motor fixing plate R8117 R8118 R8119 Fan rotor ...

Page 170: ...ith approx 5 mm left 2 Tighten the screw until it stops Then turn the screw in one scroll 3 Move the fan rotor and confirm the fan motor and the fan rotor are installed appropriately 4 Tighten the screw completely if appropriate 5 If not appropriate go back to 1 3 Press the bearing ASSY from outside 4 Remove the bearing Step Procedure Points R8120 Lock screw Fan motor R2808 Side face of rotor Side...

Page 171: ...er supplies before disassembling work Step Procedure Points 1 Appearance features Take care not to cut your finger by the fins of the outdoor heat exchanger 2 Remove the panels The stop valve cover is united with the shield plate When reassembling make sure to fit the 5 hooks 1 Remove the screw of the stop valve cover Pull down the stop valve cover and remove it DAIKIN INVERTER R7186 R7188 Stop va...

Page 172: ...ews and lift the top panel 3 Remove the drip proof plate 4 Remove the 4 screws and remove the discharge grille The discharge grille has 4 hooks Step Procedure Points DAIKIN INVERTER Top panel R7190 DAIKIN INVERTER R7191 Drip proof plate DAIKIN INVERTER R7192 Discharge grille R7193 ...

Page 173: ...move the screw and remove the drain pan heater cover 6 Remove the 7 screws of the front panel 7 Unfasten the hooks Pull and remove the front panel The front panel has 4 hooks Step Procedure Points R9329 Drain pan heater cover DAIKIN INVERTER R12304 Front panel R7195 ...

Page 174: ...e screw has reverse winding Nut size M6 1 Remove the washer fitted nut of the outdoor fan 2 Remove the outdoor fan When reassembling align mark of the outdoor fan with D cut section of the motor shaft 3 Cut the clamp Step Procedure Points R7196 Outdoor fan 10 mm R12236 R9330 D cut R7198 ...

Page 175: ...an motor lead wire through the back of the fan motor so as not to be entangled with the outdoor fan 7 Remove the 4 screws and remove the fan motor Be sure to remove the lower screws first If the upper screws are removed first the fan motor the center of gravity of which is toward the front may tilt down or fall getting you injured Step Procedure Points R9332 S70 Fan motor lead wire R7200 R7201 R32...

Page 176: ...oor Unit RXL20G2V1B Removal Procedure 161 8 Remove the screw and remove the fan motor fixing frame When reassembling fit the lower hooks into the bottom frame Step Procedure Points R9333 Fan motor fixing frame R9334 R7206 ...

Page 177: ...cedure 4 Remove the right side panel 1 Remove the 2 screws on the rear side 2 Release the outdoor temperature thermistor 3 Remove the 4 screws on the right side panel Step Procedure Points R12312 R12289 Outdoor temperature thermistor R9337 Right side panel ...

Page 178: ...163 4 Remove the screw near the stop valves 5 Unfasten the hook on the rear side When reassembling make sure to fit the hook 6 Lift up the right side panel and remove it When reassembling make sure to fit the hook Step Procedure Points R7211 R7212 R7213 Hook ...

Page 179: ...isassembling work Step Procedure Points 1 Disconnect the 2 connectors for the reactor Preparation Remove the panels and disconnect the connector for the fan motor according to the Removal of Outer Panels Fan Motor 2 Cut the clamps at 2 locations 3 Disconnect the connector for the compressor S30 When reassembling coil the excessive lead wire and hang the loop on the hook R9338 R9339 R9340 S30 ...

Page 180: ...netic relay S50 and for the thermistors S90 5 Disconnect the connectors for the filter PCB S10 and for the overload protector S40 6 Disconnect the connectors for the electronic expansion valve coil S20 and for the four way valve coil S80 Step Procedure Points R9341 S90 S50 R9342 S40 S10 R9343 S80 S20 ...

Page 181: ...the connectors for the filter PCB HL3 HN3 8 Remove the wire harness for standby electricity saving 9 Cut the clamps at 2 locations 10 Disconnect the connectors for the drain pan heater with a flat screwdriver Step Procedure Points R9344 HN3 HL3 R9345 Wire harness R9346 R9347 ...

Page 182: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 167 11 Lift and remove the electrical box Step Procedure Points R9348 Electrical box ...

Page 183: ...Remove the drain pan heater 1 Cut the clamp 2 Remove the screw of the mounting clamp 3 Release the drain pan heater ASSY from the ditch between the bottom frame and the outdoor heat exchanger ASSY Remove the wire spring with long nose pliers Take care not to cut your finger by the fins of the outdoor heat exchanger When reassembling hang the wire spring to the hair pin cooling tube R9349 R9350 Mou...

Page 184: ...or Unit RXL20G2V1B Removal Procedure 169 4 Cut the clamp 5 Remove the 3 screws and remove the left side panel 6 The fuses are inside the drain pan heater Step Procedure Points R9352 R12307 Left side panel R9354 Fuse R9355 ...

Page 185: ...power supplies before disassembling work Step Procedure Points 1 Release the discharge pipe thermistor Be careful not to lose the clip for the thermistor 2 Cut the clamp 3 Pull out the outdoor heat exchanger thermistor Be careful not to lose the clip for the thermistor R0267 Discharge pipe thermistor R12279 Clip R7221 R7222 Outdoor heat exchanger thermistor Clip ...

Page 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...

Page 187: ...l power supplies before disassembling work Step Procedure Points 1 Remove the main PCB You can remove the main PCB when you disconnect the lead wires on the terminal board without removing the electrical box 1 Feature of the main PCB 2 Remove the screw on the terminal board 3 Release the 2 earth terminals R9357 R7256 Terminal board R9358 Earth terminals ...

Page 188: ...iENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 173 4 Remove the 4 screws 5 Unfasten the 3 hooks on the upper side 6 Lift and pull out the main PCB Step Procedure Points R9359 Screws R9360 R9361 ...

Page 189: ...e main PCB Refer to page 12 for detail S10 HL3 HN3 filter PCB S20 electronic expansion valve coil S30 compressor S40 overload protector S50 magnetic relay S70 fan motor S80 four way valve coil S90 thermistors Step Procedure Points R12189 S10 S40 S90 S50 S70 S20 S80 HL3 HN3 S30 ...

Page 190: ... power supplies before disassembling work Step Procedure Points 1 Remove the reactor Preparation Remove the outer panels according to the Removal of Outer Panels Fan Motor Remove the electrical box according to the Removal of Electrical Box 1 Remove the screw and remove the reactor 2 Remove the partition plate 1 Remove the 2 screws R7224 Reactor R7225 R7226 Partition plate ...

Page 191: ...ENBE04 925_A 176 Removal Procedure 2 The partition plate has a hook on the lower side Lift and pull the partition plate to remove When reassembling fit the lower hook into the bottom frame Step Procedure Points R7227 R7228 Hook ...

Page 192: ...nd open the sound blanket outer Preparation Remove the outer panels according to the Removal of Outer Panels Fan Motor Remove the electrical box according to the Removal of Electrical Box 2 Lift and remove the sound blanket outer Since the piping ports are torn easily remove the sound blanket carefully 3 Remove the sound blanket top 4 Pull the sound blanket inner out R7229 Sound blanket outer R122...

Page 193: ...it for 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Pull out the electronic expansion valve coil 2 Remove the terminal cover 3 Disconnect the lead wires of the compressor R7233 Electronic expansion valve coil R7234 Terminal cover V W U R7235 Red U Yellow V Blue W ...

Page 194: ...dation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this wrap the four way valve with wet cloth and provide water so that the cloth does not dry In case of difficulty with gas brazing machine 1 Disconnect the brazed part where is easy to disconnect and restore 2 Cut ...

Page 195: ...tting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Step Procedure Points R7250 ...

Page 196: ...environment protection do not discharge the refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Cautions for restoration 1 Restore the piping by non oxidation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this wrap the four way valve with we...

Page 197: ...comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Be careful so as not to burn the compressor terminals the name plate the heat exchanger fin 4 Lift the compressor up and remove it Step Procedure Points R12032 Suction side R72...

Page 198: ...e disassembling work Step Procedure Points 1 Appearance features Take care not to cut your finger by the fins of the outdoor heat exchanger 2 Remove the panels The stop valve cover is united with the shield plate When reassembling make sure to fit the 5 hooks 1 Remove the screw of the stop valve cover Pull down the stop valve cover and remove it DAIKIN INVERTER R7186 R12288 R7188 Stop valve cover ...

Page 199: ...ews and lift the top panel 3 Remove the drip proof plate 4 Remove the 4 screws and remove the discharge grille The discharge grille has 4 hooks Step Procedure Points DAIKIN INVERTER Top panel R7190 DAIKIN INVERTER R7191 Drip proof plate DAIKIN INVERTER R7192 Discharge grille R7193 ...

Page 200: ...e the screw and remove the drain pan heater cover 6 Remove the 7 screws of the front panel 7 Unfasten the hooks Pull and remove the front panel The front panel has 4 hooks Step Procedure Points R9329 Drain pan heater cover DAIKIN INVERTER R12304 Front panel R11826 Hooks ...

Page 201: ... size M6 1 Remove the washer fitted nut of the outdoor fan 2 Remove the outdoor fan When reassembling align mark of the outdoor fan with D cut section of the motor shaft 3 Release the outdoor temperature thermistor Step Procedure Points R11827 Outdoor fan 10 mm R12236 R12308 D cut R12289 Outdoor temperature thermistor ...

Page 202: ...or Unit RXL20G2V1B9 Removal Procedure 187 4 Cut the clamp 5 Disconnect the connector for the fan motor S70 6 Release the fan motor lead wire from the hook Step Procedure Points R11830 R11831 S70 R11832 Fan motor lead wire ...

Page 203: ...1B9 SiENBE04 925_A 188 Removal Procedure 7 Remove the screw and remove the fan motor fixing frame When reassembling fit the lower hooks into the bottom frame Step Procedure Points R12309 Fan motor fixing frame R12310 R7206 ...

Page 204: ...n reassembling put the fan motor lead wire through the back of the fan motor so as not to be entangled with the outdoor fan 9 Remove the 4 screws and remove the fan motor 4 Remove the right side panel 1 Remove the 2 screws on the rear side Step Procedure Points R11835 R3249 Lead wire Outdoor fan R12311 Fan motor R12312 ...

Page 205: ... Removal Procedure 2 Remove the 4 screws on the right side panel 3 Remove the screw near the stop valves 4 Unfasten the hook on the rear side When reassembling make sure to fit the hook Step Procedure Points R9337 Right side panel R11839 R11842 ...

Page 206: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B9 Removal Procedure 191 5 Lift up the right side panel and remove it When reassembling make sure to fit the hook Step Procedure Points R12272 Hook ...

Page 207: ...upplies before disassembling work Step Procedure Points 1 Disconnect the connector for the overload protector S40 Preparation Remove the panels and disconnect the connector for the fan motor according to the Removal of Outer Panels Fan Motor 2 Disconnect the connector for the four way valve coil S80 3 Disconnect the 2 connectors for the reactor R11846 S40 R11848 S80 R11844 ...

Page 208: ...or the compressor 5 Disconnect the connector for the electronic expansion valve coil S20 6 Cut the clamp 7 Pull out the outdoor heat exchanger thermistor Be careful not to lose the clip for the thermistor Step Procedure Points R11845 R11847 S20 R11850 R11851 Outdoor heat exchanger thermistor Clip ...

Page 209: ...harge pipe thermistor Be careful not to lose the clip for the thermistor 9 Disconnect the connectors for the drain pan heater with a flat screwdriver 10 Lift and remove the electrical box Step Procedure Points Discharge pipe thermistor R11849 R12279 Clip R9347 R11852 Electrical Box ...

Page 210: ...Remove the drain pan heater 1 Cut the clamp 2 Remove the screw of the mounting clamp 3 Release the drain pan heater ASSY from the ditch between the bottom frame and the outdoor heat exchanger ASSY Remove the wire spring with long nose pliers Take care not to cut your finger by the fins of the outdoor heat exchanger When reassembling hang the wire spring to the hair pin cooling tube R9349 R9350 Mou...

Page 211: ...0G2V1B9 SiENBE04 925_A 196 Removal Procedure 4 Cut the clamp 5 Remove the 3 screws and remove the left side panel 6 The fuses are inside the drain pan heater Step Procedure Points R9352 R12307 Left side panel R9354 Fuse ...

Page 212: ... power supplies before disassembling work Step Procedure Points 1 Remove the main PCB You can remove the main PCB when you disconnect the lead wires on the terminal board without removing the electrical box 1 Feature of the main PCB 2 Remove the screw on the terminal board 3 Release the 2 earth terminals R11853 R11854 Terminal board R11855 Earth terminal ...

Page 213: ...ration button PCB Disconnect the connector S110 to remove the forced operation button PCB Be careful of a sharp protrusion at the back of the forced operation button PCB 5 Disconnect the relay connector 6 Cut the clamp Step Procedure Points R11856 Forced operation button PCB R11857 R11858 ...

Page 214: ...4 925_A Outdoor Unit RXL20G2V1B9 Removal Procedure 199 7 Release the harness 8 Cut the clamps at the 2 locations 9 Disconnect the connector for the filter PCB S10 Step Procedure Points R11859 R11860 R11861 S10 ...

Page 215: ...or the magnetic relay S50 and for the forced operation button PCB S100 11 Disconnect the connector for the filter PCB HL3 HN3 12 Release the harnesses from the hook 13 Release the harness for the outdoor temperature thermistor Step Procedure Points R11862 S100 S50 HL3 HN3 R11863 R11864 R11865 ...

Page 216: ...move the main PCB Refer to page 14 for detail S10 HL3 HN3 filter PCB S20 electronic expansion valve coil S40 overload protector S50 magnetic relay S70 fan motor S80 four way valve coil S90 thermistors S100 forced operation button PCB Step Procedure Points R11866 R11867 R11868 S50 S100 S90 S10 HN3 HL3 S80 S20 S40 S70 ...

Page 217: ...L20G2V1B9 SiENBE04 925_A 202 Removal Procedure 2 Remove the filter PCB 1 Release the harnesses from the hook 2 Cut the clamp 3 Release the harnesses from the hook Step Procedure Points R11869 Filter PCB R11871 R11872 ...

Page 218: ...door Unit RXL20G2V1B9 Removal Procedure 203 4 Release the harnesses from the hooks 5 Remove the screw 6 Unfasten the 2 hooks 7 Lift and pull out the filter PCB Step Procedure Points R11873 R11874 R11876 Filter PCB R11877 ...

Page 219: ...Outdoor Unit RXL20G2V1B9 SiENBE04 925_A 204 Removal Procedure 8 Feature of the filter PCB Refer to page 14 for detail Step Procedure Points R11878 ...

Page 220: ...power supplies before disassembling work Step Procedure Points 1 Remove the reactor Preparation Remove the outer panels according to the Removal of Outer Panels Fan Motor Remove the electrical box according to the Removal of Electrical Box 1 Remove the screw and remove the reactor 2 Remove the partition plate 1 Remove the 2 screws R11879 Reactor R11880 R12273 Partition plate ...

Page 221: ...SiENBE04 925_A 206 Removal Procedure 2 The partition plate has a hook on the lower side Lift and pull the partition plate to remove When reassembling fit the lower hook into the bottom frame Step Procedure Points R12280 R11883 ...

Page 222: ...e after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the sound blanket top Since the piping ports are torn easily remove the sound blanket carefully 2 Untie the string and open the sound blanket outer 3 Lift and remove the sound blanket outer R11884 Sound blanket top R11885 Sound blanket outer R11886 ...

Page 223: ...oor Unit RXL20G2V1B9 SiENBE04 925_A 208 Removal Procedure 4 Pull the sound blanket inner out 5 Pull the sound blanket bottom out Step Procedure Points R11887 Sound blanket inner Sound blanket bottom R11888 ...

Page 224: ...wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Pull out the electronic expansion valve coil 2 Remove the terminal cover 3 Disconnect the lead wires of the compressor R7233 Electronic expansion valve coil R7234 Terminal cover V W U R7235 Red U Yellow V Blue W ...

Page 225: ...idation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this wrap the four way valve with wet cloth and provide water so that the cloth does not dry In case of difficulty with gas brazing machine 1 Disconnect the brazed part where is easy to disconnect and restore 2 Cut...

Page 226: ...utting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Step Procedure Points R7250 ...

Page 227: ...ironment protection do not discharge the refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Cautions for restoration 1 Restore the piping by non oxidation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this wrap the four way valve with wet c...

Page 228: ...ns because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Be careful so as not to burn the compressor terminals the name plate the heat exchanger fin 4 Lift the compressor up and remove it R12032 Suction side R7...

Page 229: ...ter Panels Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Appearance features 2 Remove the panels 1 Remove the screw and remove the drain pan heater cover DAIKIN INVERTER R7186 R12288 R9329 Drain pan heater cover ...

Page 230: ...Remove the 4 screws and remove the discharge grille When reassembling make sure to fit the 4 hooks 4 Remove the screw and remove the stop valve cover The stop valve cover is united with the shield plate When reassembling make sure to fit the 5 hooks Step Procedure Points R12305 Top panel Hooks Hooks Discharge grille Front panel R9364 R8139 Stop valve cover R12213 Shield plate ...

Page 231: ...en reassembling fasten the wires with screws on the terminal board 1 Remove the 3 screws to remove the wiring fixture Then remove the all screws to disconnect the power supply cables and the connecting wires 2 Remove the electrical box 1 Release the outdoor temperature thermistor 2 Remove the 7 screws and remove the right side panel R12192 Wiring fixture Power supply cable Connecting wire Terminal...

Page 232: ... terminal board 4 Disconnect the connectors of the drain pan heater 5 Cut the clamp 6 Disconnect the connector for the fan motor S70 For removal procedure of the fan motor lead wire refer to Removal of Outdoor Fan Fan Motor Step Procedure Points R9366 Terminal strip R9367 R9368 R0254 S70 ...

Page 233: ...nnector for the overload protector S40 8 Disconnect the connector for the electronic expansion valve coil S20 9 Disconnect the connector for the four way valve coil S80 10 Disconnect the connector for the thermistors S90 Step Procedure Points R0255 S40 R0256 S20 R0257 S80 R0258 S90 ...

Page 234: ...compressor 12 Disconnect the 2 connectors for the reactor 13 Release the discharge pipe thermistor Be careful not to lose the clip for the thermistor 14 Detach the clamp for the thermistors from the electrical box Step Procedure Points R0259 R0260 R12197 Discharge pipe thermistor R12279 Clip R0262 R12196 ...

Page 235: ...Outdoor Unit RXL25G2V1B SiENBE04 925_A 220 Removal Procedure 15 Remove the screw in front of the electrical box 16 Lift and remove the electrical box Step Procedure Points R0263 R0264 ...

Page 236: ...Step Procedure Points 1 Remove the screw and remove the electrical box cover Preparation Remove the panels according to the Removal of Outer Panels Remove the electrical box according to the Removal of Electrical Box 2 Detach the insulation sheet The trimmed part goes front 3 Remove the 2 screws of the earth terminals R12274 Electrical box cover R8156 R8157 Insulation sheet Earth terminals R8158 ...

Page 237: ...edure 4 Release the earth wire from the hook 5 Remove the 2 screws and detach the 1 clip to remove the radiation shield plate 6 Cut off the 5 clamps and disconnect the wire harnesses Step Procedure Points R8159 R12198 Clip Radiation shield plate R8161 R8162 ...

Page 238: ...ve the 8 screws in total to remove the PCB 8 Lift up the back side slightly and unfasten the hooks of the front When reassembling make sure that the hooks of the electrical box are placed on the PCB 9 Lift up the PCB Step Procedure Points R8163 R8164 R8166 Hooks R8167 ...

Page 239: ... 10 Remove the PCB 11 Detach the terminals from the terminal board Refer to page 16 for detail S20 electronic expansion valve coil S40 overload protector S70 fan motor S80 four way valve coil S90 thermistors Step Procedure Points R8168 R8169 S70 S40 S90 S20 S80 ...

Page 240: ...SiENBE04 925_A Outdoor Unit RXL25G2V1B Removal Procedure 225 12 Remove the screw of the radiation fin Step Procedure Points R12214 Radiation fin R8171 ...

Page 241: ...Remove the drain pan heater 1 Cut the clamp 2 Remove the screw of the mounting clamp 3 Release the drain pan heater ASSY from the ditch between the bottom frame and the outdoor heat exchanger ASSY Remove the wire spring with long nose pliers Take care not to cut your finger by the fins of the outdoor heat exchanger When reassembling hang the wire spring to the hair pin cooling tube R9369 R9350 Mou...

Page 242: ...or Unit RXL25G2V1B Removal Procedure 227 4 Cut the clamp 5 Remove the 3 screws and remove the left side panel 6 The fuses are inside the drain pan heater Step Procedure Points R9352 R12307 Left side panel R9354 Fuse R9355 ...

Page 243: ...ning off all power supplies before disassembling work Step Procedure Points 1 Remove the partition plate When reassembling fit the lower hook into the bottom frame 1 Remove the 2 screws 2 The partition plate has hooks on the lower side Lift and pull the partition plate to remove R12282 Partition plate R8174 R8175 Remove the screw to remove the reactor ...

Page 244: ...lanket carefully 1 Untie the string open the sound blanket outer and pull it out 2 Remove the sound blanket top upper 3 Remove the sound blanket top lower 4 Open the sound blanket inner and pull it out Step Procedure Points R12199 Sound blanket outer R8180 R12200 Sound blanket top upper R8178 Sound blanket top lower R12201 Sound blanket inner ...

Page 245: ...fore disassembling work Step Procedure Points 1 Remove the outdoor fan The screw has reverse winding Nut size M6 1 Remove the washer fitted nut of the outdoor fan 2 Remove the outdoor fan When reassembling align mark of the outdoor fan with D cut section of the motor shaft 2 Remove the fan motor 1 Disconnect the connector for the fan motor S70 R8181 10 mm R12236 R8182 D cut R8183 R8184 S70 ...

Page 246: ...Removal Procedure 231 2 The figure shows the arrangement of the fan motor lead wire 3 Remove the 1 screw of the fan motor fixing frame 4 Remove the fan motor fixing frame Step Procedure Points R8185 R12202 Fan motor fixing frame R8187 R8188 ...

Page 247: ...fan motor lead wire 6 Release the fan motor lead wire When reassembling put the fan motor lead wire through the back of the fan motor so as not to be entangled with the outdoor fan 7 Remove the 4 screws and 4 rubber vibration isolators to remove the fan motor Step Procedure Points R8189 R7627 Lead wire Outdoor fan R12215 R8190 R8191 ...

Page 248: ...re Points 1 Release the discharge pipe thermistor Be careful not to lose the clip for the thermistor 2 Cut the clamp and pull out the outdoor heat exchanger thermistor 3 The thermistors for outdoor temperature discharge pipe outdoor heat exchanger are united as one assembly 4 The figure shows the arrangement of the thermistors R8192 Discharge pipe thermistor R12279 Clip R8193 Outdoor heat exchange...

Page 249: ...er supplies before disassembling work Step Procedure Points 1 Remove the peripheries Preparation Remove the sound blanket Detach the four way valve coil and the 2 clamps and then detach the wire harnesses 1 Remove the screw and remove the four way valve coil 2 Pull out the electronic expansion valve coil 3 Remove the putty 4 Remove the terminal cover R7703 R8203 R8204 R8205 R8195 Terminal cover ...

Page 250: ...gerant gas Cautions for restoration 1 Restore the piping by non oxidation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this wrap the four way valve with wet cloth and provide water so that the cloth does not dry In case of difficulty with gas brazing machine 1 Discon...

Page 251: ...tting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Step Procedure Points R8209 ...

Page 252: ...utes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the terminal cover 2 Disconnect the lead wires of the compressor 3 Unfasten the hooks with a flat screwdriver to remove the overload protector R8195 Terminal cover R8196 Red U Yellow V Blue W U W V R8197 U W V R8198 U W V ...

Page 253: ... happen that the refrigerant oil in the compressor catches fire prepare wet cloth so as to extinguish fire immediately Caution From the viewpoint of global environment protection do not discharge the refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Before working make sure that the refrigerant gas is empty in the circuit Be sure to apply nitrogen replacement when heat...

Page 254: ...ry In case of difficulty with gas brazing machine 1 Disconnect the brazed part where is easy to disconnect and restore 2 Cut pipes on the main unit with a tube cutter in order to make it easy to disconnect Note Do not use a metal saw for cutting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get...

Page 255: ... 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the panels Take care not to cut your finger by the fins of the outdoor heat exchanger 1 Remove the 4 screws and lift the top panel 2 Remove the screw and remove the drain pan heater cover Top panel R12283 R12290 R9375 Drain pan heater cover ...

Page 256: ...he discharge grille upwards and remove it The discharge grille has 4 hooks 4 Remove the 6 screws of the front panel 5 Push the front panel and lift the shield plate to unfasten the hooks Step Procedure Points Discharge grille R5245 Front panel R12284 Shield plate R5248 쩸 Push the front panel 쩹 Lift the shield plate upwards ...

Page 257: ...e left side hooks and then the right side hook Remove the front panel Lift the front panel while pushing the left side panel inwards Lift the front panel and unfasten the right side hook When reassembling fit the right side of the front panel first Step Procedure Points R9376 ...

Page 258: ...l Procedure 243 2 Remove the stop valve cover 1 Remove the screw of the stop valve cover 2 Pull down the stop valve cover to unfasten the hooks and remove it The stop valve cover has 6 hooks Step Procedure Points Stop valve cover R5252 R9379 R9380 ...

Page 259: ...p Procedure Points 1 Remove the electrical box cover Preparation Remove the top panel and the front panel according to the Removal of Outer Panels This procedure is not necessary to remove the outdoor fan only 1 Remove the screw of the shield plate 2 Unfasten the 2 hooks and remove the shield plate 3 Unfasten the 4 hooks of the electrical box cover and remove it R5255 Shield plate Hook R12029 Elec...

Page 260: ...G2V1B Removal Procedure 245 2 Remove the fan motor 1 Detach the clamp and disconnect the connector for the fan motor S70 2 Release the fan motor lead wire from the 7 hooks Step Procedure Points R5258 R9383 S70 R9384 Fan motor lead wire ...

Page 261: ...r fan with D cut section of the motor shaft 4 Remove the lower 2 screws from the fan motor first Be sure to remove the lower screws first If the upper screws are removed first the fan motor the center of gravity of which is toward the front may tilt down or fall getting you injured 5 Then remove the upper 2 screws Step Procedure Points R5262 Outdoor fan 10 mm R12236 R9385 D cut R9386 Fan motor ...

Page 262: ... Procedure 247 6 Release the fan motor lead wire from the 2 hooks and pull the fan motor out When reassembling put the fan motor lead wire through the back of the fan motor so as not to be entangled with the outdoor fan Step Procedure Points R9387 ...

Page 263: ...es before disassembling work Step Procedure Points 1 Remove the 2 screws of the shield plate Preparation Remove the top panel and the front panel according to the Removal of Outer Panels 2 Slide the shield plate upward to unfasten the 1 hook on the bottom left and then remove the shield plate 3 Disconnect the 2 power supply cables and the 1 earth wire R9388 Shield plate R9389 R9390 ...

Page 264: ...Unit RXL35G2V1B Removal Procedure 249 4 Disconnect the 2 earth wires 5 Remove the 3 screws of the right side panel 6 Remove the screw of the electrical box Step Procedure Points R9391 Earth wires R9392 Right side panel R9393 ...

Page 265: ...y connectors of the drain pan heater 8 Unfasten the hooks and remove the right side panel When reassembling insert the 2 hooks of the lower part and the 1 hook of the upper back 9 Remove the screws of the drain pan heater harness Step Procedure Points R9394 R9395 Hook R5273 Hooks R9396 ...

Page 266: ...1 Detach the 2 wire clamps 12 Disconnect the connectors of the front side S20 electronic expansion valve coil S40 overload protector S80 four way valve coil S90 thermistors 13 Disconnect the relay connector for the compressor Step Procedure Points R9397 R9398 R5275 S40 S20 S90 S80 ...

Page 267: ...Detach the clamp and release the thermistor lead wires from the hook 15 Remove the screw 16 Release the outdoor temperature thermistor 17 Release the harness of the outdoor temperature thermistor from the hook Step Procedure Points R9400 Clamp Hook R9401 R9402 R9403 ...

Page 268: ...SiENBE04 925_A Outdoor Unit RXL35G2V1B Removal Procedure 253 18 Lift and remove the electrical box Step Procedure Points R9404 Electrical box ...

Page 269: ...work Step Procedure Points 1 Remove the cover of the electrical box Preparation Remove the electrical box according to the Removal of Electrical Box 2 Disconnect the connectors from the service monitor PCB S52 S102 3 Detach the 4 clamps with pliers 4 Remove the screws of the terminal board and the earth wire R9405 R5280 Service monitor PCB S52 S102 Clamps R5281 R12285 Terminal board Earth wire ...

Page 270: ...55 5 Unfasten the hook on the right 6 Open the terminal board 7 Disconnect the harnesses 1 Black 2 White 3 Red L1 Black L2 Brown N1 White N2 Blue 8 Disconnect the 2 connectors for the reactor HR1 HR2 Step Procedure Points R5285 N2 N1 L1 3 2 1 L2 R11473 HR2 HR1 ...

Page 271: ...SiENBE04 925_A 256 Removal Procedure 9 Remove the 3 screws of the main PCB 10 Unfasten the 4 hooks 11 Lift up and remove the main PCB Refer to page 18 for detail Step Procedure Points Main PCB R5287 R5288 Hooks Main PCB R5289 ...

Page 272: ...Remove the drain pan heater 1 Cut the clamp 2 Remove the screw of the mounting clamp 3 Release the drain pan heater ASSY from the ditch between the bottom frame and the outdoor heat exchanger ASSY Remove the wire spring with long nose pliers Take care not to cut your finger by the fins of the outdoor heat exchanger When reassembling hang the wire spring to the hair pin cooling tube R9406 R9407 Mou...

Page 273: ...V1B SiENBE04 925_A 258 Removal Procedure 4 Cut the clamp 5 Remove the 3 screws and remove the left side panel 6 The fuses are inside the drain pan heater Step Procedure Points R9352 R12307 Left side panel R9354 Fuse R9355 ...

Page 274: ...utes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the sound blanket back 2 Remove the sound blanket outer Since the piping ports are torn easily remove the sound blanket carefully 3 Remove the sound blanket top upper Sound blanket back R5293 Sound blanket outer R5294 Sound blanket top upper ...

Page 275: ...er 6 Release the discharge pipe thermistor Be careful not to lose the clip for the thermistor 7 Cut the clamp and pull out the outdoor heat exchanger thermistor Step Procedure Points Sound blanket top lower R11398 Sound blanket inner R5296 R12286 Discharge pipe thermistor R12287 Clip Outdoor heat exchanger thermistor R5292 Clamp ...

Page 276: ...toration 1 Restore the piping by non oxidation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this wrap the four way valve with wet cloth and provide water so that the cloth does not dry Note Do not use a metal saw for cutting pipes by all means because the sawdust com...

Page 277: ...y the gas brazing machine Warning If the refrigerant gas leaks during work ventilate the room If the refrigerant gas is exposed to flames toxic gas may be generated Caution From the viewpoint of global environment protection do not discharge the refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Before working make sure that the refrigerant gas is empty in the circuit B...

Page 278: ... Compressor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the terminal cover 2 Disconnect the lead wires of the compressor Terminal cover R5302 R12204 Yellow V Red U Blue W ...

Page 279: ... exposed to flames toxic gas may be generated Warning Since it may happen that the refrigerant oil in the compressor catches fire prepare wet cloth so as to extinguish fire immediately Caution From the viewpoint of global environment protection do not discharge the refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Before working make sure that the refrigerant gas is em...

Page 280: ...here is easy to disconnect and restore 2 Cut pipes on the main unit with a tube cutter in order to make it easy to disconnect Note Do not use a metal saw for cutting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame ...

Page 281: ...al Operation and Field Settings 1 Trial Operation 267 2 Field Settings 268 2 1 When 2 Units are Installed in 1 Room 268 2 2 Standby Electricity Saving 269 2 3 Jumper and Switch Settings 270 3 Application of Silicon Grease to a Power Transistor and a Diode Bridge 271 ...

Page 282: ...stem then restarts operation with the previous mode when the circuit breaker is restored In cooling mode select the lowest programmable temperature in heating mode select the highest programmable temperature Trial operation may be disabled in either mode depending on the room temperature After trial operation is complete set the temperature to a normal level 26 C to 28 C in cooling mode 20 C to 24...

Page 283: ...for different address Both the indoor unit PCB and the infrared remote control need alteration Indoor Unit PCB 1 Remove the front grille 2 screws 2 Remove the electrical box 1 screw 3 Remove the shield plate 4 hooks 4 Cut the address setting jumper JA on the control PCB Infrared Remote Control 1 Remove the cover and take it off 2 Cut the address setting jumper J4 ADDRESS JA ADDRESS JA EXIST 1 CUT ...

Page 284: ...rocedure is required for turning ON the function 1 Check that the main power supply is turned OFF Turn OFF if it has not been turned OFF 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn ON the main power supply Caution Before connecting or disconnecting the selective connector for standby electricity saving make sure that the main power suppl...

Page 285: ...n speed setting Remote control setting Fan rpm is set to 0 Fan stop JC on indoor unit PCB Power failure recovery function Auto restart The unit does not resume operation after recovering from a power failure Timer ON OFF settings are cleared J5 on outdoor unit PCB of 20 25 class Improvement of defrost performance Standard control Reinforced control ex The frequency increases the duration time of d...

Page 286: ...for encouraging the heat radiation of the power transistor and the diode bridge Applying the paste should be implemented in accordance with the following instruction Remark There is the possibility of failure with smoke in case of bad heat radiation Wipe off the old silicon grease completely on a radiation fin Apply the silicon grease evenly to the whole Do not leave any foreign object such as sol...

Page 287: ...SiENBE04 925_A 272 Appendix Part 9 Appendix 1 Piping Diagrams 273 1 1 Indoor Unit 273 1 2 Outdoor Unit 274 2 Wiring Diagrams 276 2 1 Indoor Unit 276 2 2 Outdoor Unit 276 ...

Page 288: ...REFRIGERANT FLOW FIELD PIPING 9 5CuT 6 4CuT FIELD PIPING M COOLING INDOOR UNIT FAN MOTOR HEAT EXCHANGER 6 4CuT HEATING THERMISTOR ON HEAT EXCH 4D058897C CROSS FLOW FAN COOLING 9 5CuT 6 4CuT M INDOOR UNIT 6 4CuT REFRIGERANT FLOW HEATING FAN MOTOR FIELD PIPING HEAT EXCHANGER FIELD PIPING 12 7CuT THERMISTOR ON HEAT EXCH 4D058898C ...

Page 289: ...FLOW 7 0CuT COOLING φ 4 0 ID 2 0CuT 4 8CuT PROPELLER FAN COMPRESSOR OUTDOOR UNIT 9 5CuT 6 4CuT 4 8CuT 9 5CuT MUFFLER ACCUMULATOR 9 5CuT 3D059586E 3D059590A OUTDOOR UNIT HEAT EXCHANGER 7 9CuT 7 9CuT 12 7CuT 9 5CuT PROPELLER FAN 7 9CuT 7 9CuT MUFFLER DISCHARGE PIPE THERMISTOR FOUR WAY VALVE ON HEATING COMPRESSOR ACCUMULATOR 9 5CuT 9 5CuT 9 5CuT 9 5CuT HEAT EXCHANGER THERMISTOR 4 8CuT 4 8CuT 6 4CuT M...

Page 290: ... 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT PROPELLER FAN MUFFLER HEAT EXCHANGER 7 9CuT 7 9CuT M COMPRESSOR 12 7CuT 12 7CuT 7 9CuT 7 9CuT 4 0CuT 4 0CuT CAPILLARY TUBE 4 CAPILLARY TUBE 2 CAPILLARY TUBE 3 CAPILLARY TUBE 1 9 5CuT MUFFLER 9 5CuT 6 4CuT 12 7CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT FILTER RECEIVER FIELD PIPING FIELD PIPING REFRIGERANT FLOW 12 7 CuT 6 4 CuT HEATING COOLING 4 0Cu...

Page 291: ...V2 V3 SA1 YLW GRN E1 E2 Z2C N 2 outdoor FU4 1A FU5 1A E1H t S1T DRAIN PAN HEATER L1 PCB1 MR30 MR30_A MR30_B MRM20 MRM10 HR1 HN2 HL2 1 S11 9 BLK BLK BRN BRN 4 1 BLK BLK ORG BLU GRY WHT BLK BLK BLK BLK BLK BLK BLK BLK L1R ORG HN3 HL3 1 S10 FU1 3 15A 9 2 1 S50 S20 S40 1 6 2 1 MRCW 1 3 S80 V1 WHT YLW ORG BLU BRN RED BLK GRY BLU BLU Y1E M S90 S70 NOTE 1 REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS...

Page 292: ...DGE HEATER FUSE INTELLIGENT POWER MODULE LIVE COIL REACTOR COMPRESSOR MOTOR FAN MOTOR MAGNETIC RELAY NEUTRAL PROTECTIVE EARTH SA1 OVERLOAD PROTECTOR PRINTED CIRCUIT BOARD CONNECTOR THERMISTOR THERMO STAT SURGE ARRESTER DRAIN PAN HEATER IN CASE OF COOLING ONLY TYPE 3D065716A 3D062388 indoor 1 2 3 L N X1M L N 1 2 3 WHT WHT outdoor FU4 1A FU5 1A E1H t S1T DRAINPAN HEATER FIELD WIRING GRN YLW GRN Z2C ...

Page 293: ...01 1 5 S102 1 5 PCB2 S2 LED A SW1 SW4 Y1R S80 3 1 BLU BLU INCASEOF HEAT PUMP TYPE S20 1 6 WHT YLW ORG BLU BRN RED M Y1E outdoor 1 S90 6 BLK BLK BLK t t t OUTDOOR DISCHARGE CONDENSER R3T R2T R1T Z1C Z5C FERRITE CORE X1M X2M TERMINAL STRIP MRM10 MRM20 L LIVE M1C COMPRESSOR MOTOR Y1E ELECTRONIC EXPANSION VALVE COIL MRC W MAGNETIC RELAY N NEUTRAL M1F FAN MOTOR V2 V3 V5 V6 V11 VARISTOR R1T R3T THERMIST...

Page 294: ...lication to the best of its knowledge No express or implied warranty is given for the completeness accuracy reliability or fitness for particular purpose of its content and the products and services presented therein Specifications are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage In the broadest sense arising from or re...