ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Network Control Property
Keypad attributes available as BACnet
Standard Objects for network control
of the unit
Page
R = Read W = W
rite
Object T
ype
Object Instance
Description
Evaporator Pump Run Hours
Pump Select
Pump #2
R
Hours reported at 1/10th the actual hours.
AI
27
0–65,535
AI
89
0–65,535.
Evaporator Refrigerant Pressure
Compressor Select
Compressor #2
R
AI
13
-3276.8–3276.7
AI
71
-3276.8–3276.7
Evaporator Saturated Refrigerant
Temperature
Compressor Select
Compressor #2
R
AI
14
-40°–244°F
AI
70
-40°–244°F
Evaporator Water Flow Rate
R
AI
49
Flow Rate in GPM Centrifugals Only
Evaporator Water Pump Status
R
BI
36
0=No Flow, 1=Flow
Heat Recovery Entering Water
Temperature
R
AI
5
-40°–244°F
Heat Recovery Leaving Water
Temperature
R
AI
6
-40°–244°F
Heat Setpoint
W
AO
31
50–150°F, Default=95°F
Ice Setpoint
W
AO
30
15– 35°F, Default=25°F
IGV Percentage Open
Compressor #1
Compressor #2
R
0–110%
AI
58
AI
62
Inverter Temperature
Compressor #1
Compressor #2
R
AI
66
AI
87
Liquid Line Refrigerant Pressure
R
AI
12
-22592–22591 psi
Liquid Line Refrigerant Temperature
Compressor Select
Compressor #2
R
AI
11
-40°–244°F
AI
85
-40°–244°F
Maximum RPM
Compressor #1
Compressor #2
R
0–32678
AI
55
AI
59
Minimum RPM
Compressor #1
Compressor #2
R
0–32678
AI
57
AI
61
Motor Cavity Temperature
Compressor #1
Compressor #2
R
AI
65
AI
86
Oil Feed Pressure
Compressor Select
Compressor #2
R
AI
19
-22592–22591 psi
AI
81
-22592–22591 psi
Oil Feed Temperature
Compressor Select
Compressor #2
R
AI
21
-40°–244°F
AI
83
-40°–244°F
Oil Sump Pressure
Compressor Select
Compressor #2
R
AI
20
-22592–22591 psi
AI
82
-22592–22591 psi
Oil Sump Temperature
Compressor Select
Compressor #2
R
AI
22
-40°–244°F
AI
84
-40°–244°F
Outdoor Air Temperature
R
AI
10
-40°–244°F
*Boldface denotes data points for typical minimum integration.