ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Condenser Pump Run Hours
Keypad Menu Path:
No Keypad Equivalent
NOTE:
Value returned must be multiplied by 10 to give run hours.
Measurement
Units
Data Type
Valid Range
Default Value
Event Count
NA
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
0–65,535
NA
BACnet
Pump Select
This output network variable indicates the number of hours (x10) that the selected condenser pump motor has been turned on. See
. (I48)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
28
Present Value
85
Object Name
CondPumpOperHours
Pump #2
This output network variable indicates the number of hours (x10) that the selected condenser pump 2 has been turned on. Not
available on all chiller models. (I104)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
90
Present Value
85
Object Name
CondPmp2Hrs
LONWORKS
Variable Details
This output network variable indicates the number of hours (x10) that the selected condenser pump motor has been turned on. See
. (I48)
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCondPumpHrs
Proprietary
count
8
two bytes