ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Minimum RPM
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the minimum (surge) RPM. This is the speed the Turbocor compressor
calculates is the minimum safe operating speed above onset of stall. (I119 & I123)
Measurement
Units
Data Type
Valid Range
Default Value
Revolutions per Minute
BACnet: RPM
BACnet: Real
BACnet: 0–32678
NA
BACnet
Compressor #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
57
Present Value
85
Object Name
Comp1MinRPM
Compressor #2
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
61
Present Value
85
Object Name
Comp2MinRPM
LONWORKS
No LONWORKS equivalent.
Minimum Send Time
Keypad Menu Path:
No Keypad Equivalent
This configuration network parameter controls the minimum period of time that expires before objects
can be retransmitted.
Measurement
Units
Data Type
Valid Range
Default Value
Elapsed Time
seconds
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
0–6553.4 sec
0 (no automatic update)
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
SCPT_Reference
SCPT Index
nciMinSendTime
Chiller
time_sec
107
two bytes
SCPT_minSendTime
52