ED 15062-7 • MICROTECH II CHILLER CONTROLLER 42
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Compressor Run Hours
Keypad Menu Path:
Menu
\View
\Compressor
NOTE:
Value returned must be multiplied by 10 to give run hours.
Measurement
Units
Data Type
Valid Range
Default Value
Event Count
Hours
BACnet: Real
LONWORKS: Float Type
unsigned long
0–65,535
NA
BACnet
Compressor Select
This output network variable indicates the number of hours (x10) that the compressor motor of the compressor selected with
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
26
Present Value
85
Object Name
CompHours
Compressor #2
This variable indicates the number of hours (x10) for compressor 2. Not available on all chiller models. (I107)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
93
Present Value
85
Object Name
Comp2Hours
Compressor #3
This variable indicates the number of hours (x10) for compressor 3. Not available on all chiller models. (I110)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
101
Present Value
85
Object Name
Comp3Hours
Compressor #4
This variable indicates the number of hours (x10) for compressor 4. Not available on all chiller models. (I113)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
109
Present Value
85
Object Name
Comp4Hours
LONWORKS
This output network variable indicates the number of hours (x10) that the compressor motor of the compressor selected with
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCompHrs
Proprietary
count
8
two bytes