ED 15062-7 • MICROTECH II CHILLER CONTROLLER 28
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Chiller Limited
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the main running mode and states of the Chiller. The Limited
network variable indicates whether conditions exist that prevent the chiller from reaching setpoint. (D6)
Measurement
Units
Data Type
Valid Range
Default Value
Status
NA
BACnet: Enumerated
LONWORKS: Structure
See Below
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
39
Present Value
85
Object Name
ChillerLimited
Property Values
0 = Not Limited(Inactive)
1 = Limited(Active)
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network variable output (see
).
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChillerStat
Chiller
chlr_status
127
3 bytes
Chiller Local/Remote
Keypad Menu Path:
No Keypad Equivalent
The Local/Remote network variable indicates whether the chiller is in local control or allowed to be
controlled remotely over the network. (D5)
Measurement
Units
Data Type
Valid Range
Default Value
Mode
NA
BACnet: Enumerated
LONWORKS: Structure
See Below
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
38
Present Value
85
Object Name
ChillerLocalRemote
Property Values
0 = Remote
1= Local
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network output variable (see
).
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
Data Type
nvoChillerStat
Chiller
chlr_status
127
3 bytes
Structure