ED 15062-7 • MICROTECH II CHILLER CONTROLLER 96
www.DaikinApplied.com
a
larms
-
a
larms
-
Two LONWORKS network variables indicate alarm conditions
and one network variable clears alarms. The Chiller Status
network output variable indicates that the unit controller is in
alarm, but it does not identify the alarm condition. The Current
Alarm network output variable indicates the alarm condition.
Current Alarm
Keypad Menu Path:
Menu
\Alarm
\Active
This network output variable indicates the current alarm. The type of alarm is included in the text
string. Alarm messages are listed in
. The unit controller can accommodate 15
simultaneous alarms. Alarm messages are sent sequentially one every five seconds.
Measurement
Units
Data Type
Valid Range
Default Value
Alarm Message
NA
Structure
0–30 characters plus a NUL
terminator
NA
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoAlarmDescr
Chiller
str_asc
36
31 bytes max
Structure
typedef struct {
unsigned char ascii[31];
} SNVT_str_asc;