ED 15062-7 • MICROTECH II CHILLER CONTROLLER 20
www.DaikinApplied.com
C
omPrehensIve
d
aTa
P
oInT
T
ables
Network Input Variables
Network Control Property
Keypad attributes available
as LONWORKS Variables for
network control of the unit
Variable Name
Page
SNVT
Index
Description
*Capacity Limit Setpoint (10)
nviCapacityLim
81
0 to 160%; Default=100%
*Chiller Enable (Input) (4)
nviChillerEnable
95
0=Request Chiller OFF, 1=Request Chiller On; Default=OFF
Chiller Mode Setpoint
nviMode
108
1=HVAC_HEAT, 3=HVAC_COOL, 5=HVAC_PRE_COOL, 11=HVAC_ICE;
Default=Cool
Compressor Select
nviCompSelect
8
See Variable Description
*Cool Setpoint (9)
nviCoolSetpt
105
-12 .2– 48 .8°C; Default=7 .2°C
Heat Setpoint
nviHeatSetpt
105
10–93°C; Default=35°C
Ice Setpoint
nviIceSpt
105
-9.4– 1.7°C; Default=-3.9°C
*Network Clear Alarm (12)
nviClearAlarm
95
0= Inactive,1=Clear Alarm; Default=0
Pump Select
nviPumpSelect
95
0=Pump No. 1, 1=Pump No. 2; Default=0
*Boldface denotes data points for typical minimum integration.
Network Configuration Parameters
Network Control Property
Keypad attributes available as LONWORKS
Variables for network control of the unit
Variable Name
Page
SCPT_Reference
SCPT
Index Description
Default Value
Capacity Limit (LONWORKS Configuration)
nciCapacityLim
SCPT_limitChlrCap
81
0% to 160%.
100%
Chiller Enable (LONWORKS Configuration)
nciChillerEnable
SCPT_pwrUpState
73
0=Request Chiller OFF, 1=Request
Chiller Auto (run)
0
Cool Setpoint (LONWORKS Configuration)
nciCoolSetpt
SCPT_CoolSetpoint
75
-40°C to 93°C
7.2°C
Default Values
nciDefaults
59 SCPT_maxSendTime
71
0=Use Default Values, 1=Use
Manufacturer-Specified Values
0
Heat Setpoint (LONWORKS Configuration)
nciHeatSetpt
SCPT_HeatSetpoint
78
-40–93°C
37.8°C
Chiller Location
nciLocation
SCPT_location
17
Any NUL terminated ASCII string up to
31 bytes.
00000
Maximum Send Time
nciMaxSendTime
76 SCPT_maxSendTime
52
0–6553.4 sec
0 sec
Minimum Send Time
nciMinSendTime
SCPT_minSendTime
52
0–6553.4 sec
0 sec
*Chiller Mode (LONWORKS Configuration) (2)
nciMode
SCPT_HVACmode
74
1=HVAC_HEAT, 3=HVAC_COOL,
11=HVAC_ICE
3
Receive Heartbeat
nciRcvHrtBt
SCPT_maxRcvTime
49
0.0–6553.4 sec (0.1 sec)
0
*Boldface denotes data points for typical minimum integration.