ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Default Values
Keypad Menu Path:
No Keypad Equivalent
This configuration network parameter determines which set of values is used on power up and
communication failure. The choice is the stated default values or a list of manufacturer specified values.
This is used for the following configuration network variables: (D10)
• Chiller Enable
• Capacity Limit
• Cool Setpoint
• Heat Setpoint
• Mode
Measurement
Units
Data Type
Valid Range
Default Value
Chiller State
NA
LONWORKS: structure
Enumerated
0 = Use Default Values
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
SCPT_Reference
SCPT Index
nciDefaults
Chiller
switch
95
two bytes
SCPT_
DefaultBehavior
71
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0
Use Default Values
1
Use Manufacturer-Specified Values