ED 15062-7 • MICROTECH II CHILLER CONTROLLER 60
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Design RPM
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the Turbocor compressors calculated speed target based on
conditions and request demand. (I125 & I126)
Measurement
Units
Data Type
Valid Range
Default Value
Revolutions per Minute
BACnet: RPM
BACnet: Real
BACnet: 0–32678
NA
BACnet
Compressor #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
63
Present Value
85
Object Name
Comp1DesignRPM
Compressor #2
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
64
Present Value
85
Object Name
Comp2DesignRPM
LONWORKS
No LONWORKS equivalent.
Device Object
CAUTION
If another device in the network has the same object identifier
(instance number), you must change the instance number of
one device object so that all devices in the network have a
unique device instance.
Keypad Menu Path:
No Keypad Equivalent
Each BACnet compatible device must have only one BACnet Device Object. The device object contains
all required properties and the Max_Master and Max_Info_Frames optional properties. All properties
of the device object may be read, but cannot be changed over the network. The initial instance of the
MicroTech II Chiller device object is 3000. All critical properties of the device object can be changed in
the HTTP Interface. The device object name is first part of the full reference to all objects in the BACnet
Communication Module.
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Device
8
3000
Object Name
MTII Chiller UC 3000