ED 15062-7 • MICROTECH II CHILLER CONTROLLER 32
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Chiller ON OFF
Keypad Menu Path:
Menu
\View
\Unit
\Status
This output network variable indicates the current state of the chiller. The OFF state is represented by
state = FALSE and value = 0. The other discrete states are represented by state = TRUE and value > 0.
It is normally recommended to monitor the “Chiller Status” data point for the current operating state of
the chiller. (D2)
Measurement
Units
Data Type
Valid Range
Default Value
Chiller State
NA
LONWORKS: structure
See Below
NA
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network variable output (see
).
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoOnOff
Chiller
switch
06
two bytes
Chiller Power
Keypad Menu Path:
No Keypad Equivalent
This variable indicates the totalized compressor kilowatts. (I116).
Measurement
Units
Data Type
Valid Range
Default Value
Percent of chiller capacity
NA
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
0–160%
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
67
Present Value
85
Object Name
TotalChillerKW
LONWORKS
No LONWORKS equivalent.