ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Chiller Location
Keypad Menu Path:
No Keypad Equivalent
This configuration network parameter provides a description of the location.
Measurement
Units
Data Type
Valid Range
Default Value
NA
NA
Structure
Any NUL terminated ASCII
string up to 31 bytes.
ASCII string of zeros + NUL
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
SCPT_Reference
SCPT Index
nciLocation
Chiller
str_asc
36
31 bytes max
SCPT_location
17
Structure
typedef struct {
unsigned char ascii[31];
} SNVT_str_asc;
Chiller Mode
Keypad Menu Path:
No Keypad Equivalent
This LONWORKS configuration network parameter establishes the default operating mode of the chiller,
unless the configuration parameter nciDefaults = 1 (See
). If nciDefaults =
1, the default values are the values specified during manufacturing.
• Heat Mode
• Cool Mode (default)
• Ice Mode
Measurement
Units
Data Type
Valid Range
Default Value
HVAC Mode
NA
Unsigned Integer
Enumerated
See Below
LONWORKS
Default Value
3 = HVAC_COOL
The chiller object uses the configuration value of nciMode on power-up or loss of communication unless the configuration
parameter nciDefaults =1 (See
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
SCPT Reference
SCPT Index
nciMode
Chiller
hvac_mode
108
one byte
SCPT_HVACmode
74