d
eTaIled
d
aTa
P
oInT
I
nformaTIon
www.DaikinApplied.com
43
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor Select
Keypad Menu Path:
No Keypad Equivalent
This input network variable selects the compressor/circuit (number 1, 2, 3, 4, 5 or 6) that is interrogated.
The controller returns the information for the selected compressor/circuit. You must first select a
compressor/circuit then interrogate the selected compressor/circuit. This variable selects a compressor/
circuit for the following variables. See
(Data Points for Chiller Models) to
determine which of these variables will be available. (I32)
Name
Page
Name
Page
Compressor Current
36
Evaporator Leaving Water Temperature for Compressor
57
Compressor Discharge Temperature
38
Evaporator Refrigerant Pressure
58
Compressor Percent RLA
39
Evaporator Saturated Refrigerant Temperature
59
Compressor Power
40
Liquid Line Refrigerant Pressure
63
Compressor Run Hours
41
Liquid Line Refrigerant Temperature
65
Compressor Starts
43
Oil Feed Pressure
67
Compressor Status
44
Oil Feed Temperature
68
Compressor Voltage
46
Oil Sump Pressure
69
Condenser Refrigerant Pressure
50
Oil Sump Temperature
69
Condenser Saturated Refrigerant Temperature
51
Measurement
Units
Data Type
Valid Range
Default Value
Event Count
NA
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
1–6
Comp No. 1
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Multi-state Output
14
46
Present Value
85
Object Name
CompSelect
Property Values
1 = Comp/Circuit No. 1
2 = Comp/Circuit No. 2
3 = Comp/Circuit No. 3 (Circuit No. 1 on Scroll Chillers and Condensing Units)
4 = Comp/Circuit No. 4 (Circuit No. 2 on Scroll Chillers and Condensing Units)
5 = Comp No. 5 (Circuit No. 1 on Scroll Chillers and Condensing Units)
6 = Comp No. 6 (Circuit No. 2 on Scroll Chillers and Condensing Units)
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nviCompSelect
Proprietary
count
8
two bytes
Valid Range
1 = Comp/Circuit No. 1
2 = Comp/Circuit No. 2
3 = Comp/Circuit No. 3 (Circuit No. 1 on Scroll Chillers and Condensing Units)
4 = Comp/Circuit No. 4 (Circuit No. 2 on Scroll Chillers and Condensing Units)
5 = Comp No. 5 (Circuit No. 1 on Scroll Chillers and Condensing Units)
6 = Comp No. 6 (Circuit No. 2 on Scroll Chillers and Condensing Units)