ED 15062-7 • MICROTECH II CHILLER CONTROLLER
MicroTech II Chiller Unit Controller
Device Object
Each BACnet compatible device must have one and only one
BACnet Device Object.
Device Object Identifier
The MicroTech II Chiller Unit Controller Device Object Identifier
uniquely specifies the unit within the network. The device
object type for all devices is fixed by ASHRAE at 8. Therefore
the device object instance number must be unique. The initial
Device Object identifier is set at 3000 during manufacturing.
The device object identifier can be read from the unit controller.
The name of the property is “Object_Identifier” and the property
identifier is 75.
CAUTION
If another device in the network already has this object
identifier (instance number), you must change the instance
number of one device object so that all devices in the network
have a unique device identifier.
Device Object Name
The Device Object Name uniquely specifies a device in the
network. It must be unique in the network. The device name
for the MicroTech II Chiller Unit Controller device is MTII Chiller
UC ####. The #### represents the device object instance
number. The device name is the “prefix” of all object names in
the MicroTech II Chiller Unit Controller. All objects include the
device name and a period “.” (MTII Chiller UC ####.) preceding
the object name. The device object instance number assigned
at manufacturing is 3000.
NOTE:
If you change the device instance in the HTTP
Interface, you also change the device name and thus
the full reference for all objects in the unit controller.
The Device Object name is also available to the network in
the device. The property name is “Object_Name” and property
identifier is 77.
Network Considerations
Access to Properties
To access a property, you must specify the object identifier,
including the device object identifier or the object name, in
addition to the device object name and the property identifier.
Configuring the Unit Controller
The MicroTech II Chiller Unit Controller, along with the
BACnet Communication Module, are designed, programmed,
and configured at the factory to be a chiller unit controller
accessible over a BACnet network. No additional programming
is required to make this a chiller unit controller. The unit
controller is ready to operate with the default values of the
various parameters set at the factory.
Default values may be changed with the unit keypad or via the
network.
The BACnet Configuration Tool is required to set baud rate,
device instance number, and the MAC address, particularly
with multiple chillers on a single network. The BACnet
Configuration Tools is available as a free download on
. Refer to
the BACnet Configuration Tool to set network parameters.
See the appropriate Operation Manual for default values and
keypad operating instructions and the BACnet Communication
Module Installation Manual (see Reference Documents section
for literature part numbers.) The Installation Manual specifies
default values for variables accessible from the network.