ED 15062-7 • MICROTECH II CHILLER CONTROLLER 62
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Evaporator Flow Switch Status
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the status of water flow through the evaporator. (D7)
Measurement
Units
Data Type
Valid Range
Default Value
Flow State
NA
BACnet: Enumerated
LONWORKS: Structure
See Below
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
34
Present Value
85
Object Name
EvapWaterFlowStatus
Property Values
0 = No Flow(Inactive)
1 = Flow(Active)
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChWFlow
Proprietary
switch
95
two bytes
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field
unused
State Field
0
No Flow
1
Flow