ED 15062-7 • MICROTECH II CHILLER CONTROLLER 40
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Compressor Power
Keypad Menu Path:
No Keypad Equivalent
Measurement
Units
Data Type
Valid Range
Default Value
Power
kiloWatts
BACnet: Real
LONWORKS: Unsigned Long
0-6553.5
NA
BACnet
Compressor Select
. (A27)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
54
Present Value
85
Object Name
Kilowatts
Compressor #2
This variable indicates the current power for the compressor motor of compressor 2. It is available via BACnet only.(A96)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
77
Present Value
85
Object Name
Comp2Kilowatts
Compressor #3
This variable indicates the current power for the compressor motor of compressor 3. It is available via BACnet only.(A108)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
96
Present Value
85
Object Name
Comp3Kilowatts
Compressor #4
This variable indicates the current power for the compressor motor of compressor 4. It is available via BACnet only.(A113)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
104
Present Value
85
Object Name
Comp4Kilowatts
Compressor #5
This variable indicates the current power for the compressor motor of compressor 5. It is available via BACnet only.(A118)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
112
Present Value
85
Object Name
Comp5Kilowatts