ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Pump Select
Keypad Menu Path:
No Keypad Equivalent
This input network variable selects which pump (Number 1 or Number 2) supplies the data. The
controller returns the information for the appropriate Condenser or Evaporator pump. You must first
select a pump and then interrogate the selected pump. See
Condenser Pump Run Hours on page 53
Evaporator Pump Run Hours on page 65
Measurement
Units
Data Type
Valid Range
Default Value
Event Count
NA
BACnet: Unsigned Integer
LONWORKS: structure
See Below
BACnet : 1 = Pump No. 1
LONWORKS: 0 = Pump No. 1
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Multi-state Output
14
47
Present Value
85
Object Name
PumpSelect
Property Values
1 = Pump #1
2 = Pump #2
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nviPumpSelect
Proprietary
Switch
95
two bytes
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field
unused
State Field
0
Pump No. 1
1
Pump No. 2