ED 15062-7 • MICROTECH II CHILLER CONTROLLER 72
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Ice Setpoint
Keypad Menu Path:
Menu
\Set
\Unit SPs (3)
The Ice Setpoint data point determines the temperature of the Leaving Chilled Water. LONWORKS
network variables set the operating Temperature. The BACnet property is a commandable property of a
Analog Output object. Refer to the appropriate Operation Manual for suitable variable values. (A30)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
Dependent on Chiller Mode
and Model
See below
BACnet
This commandable property sets the temperature of the Leaving Chilled Water. This level may be adjusted via an operator
workstation or other network device. When this property is read, it indicates the current value of the temperature of the Leaving
Chilled Water.
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Output
1
30
Present Value
85
Object Name
NetworkIceTempSetpoint
Default Value (Relinquish_Default)
25°F
LONWORKS
Input (nvi)
This input network variable provides the Ice setpoint of the Leaving Chilled Water when the chiller is operating in the Ice Mode.
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nviIceSpt
Chiller
temp_p
105
two bytes
Default Value
-3.9°C