ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Oil Sump Pressure
Keypad Menu Path:
No Keypad Equivalent
Measurement
Units
Data Type
Valid Range
Default Value
Pressure
BACnet: psi
LONWORKS: kPa
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
BACnet: -22592–22591 psi
LONWORKS:
-3,276.8…3,276.7 kPa
NA
BACnet
Compressor Select
This output network variable indicates the current compressor oil sump pressure. There is a separate output for each compressor.
. (A33)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
20
Present Value
85
Object Name
OilSumpPressure
Compressor #2
This variable indicates the current compressor oil sump pressure for compressor 2. Not available on all chiller models. (A101)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
82
Present Value
85
Object Name
Comp2OilSumpPress
LONWORKS
Variable Details
This output network variable indicates the current compressor oil sump pressure. There is a separate output for each compressor.
. (A33)
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoOilSumpPress
Proprietary
press
30
two bytes