ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Evaporator Saturated Refrigerant Temperature
Keypad Menu Path:
Menu
\Unit
\Refrigerant (1)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See
. (A16)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
14
Present Value
85
Object Name
EvapSatTemp
Compressor #2
This output network variable indicates the current saturated refrigerant temperature in the evaporator for compressor 2. (A89) Not
available on all chiller models.
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
70
Present Value
85
Object Name
Comp2EvapSatRTmp
LONWORKS
Variable Details
This output network variable indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See
. (A16)
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoSatEvapRefTemp
Proprietary
temp_p
105
two bytes