ED 15062-7 • MICROTECH II CHILLER CONTROLLER 70
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Heat Recovery Entering Water Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current temperature of the water entering the heat recovery
section. (A22)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS:-40°–118°C
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
5
Present Value
85
Object Name
HeatRecEntWaterTemp
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoEntHRWTemp
Proprietary
temp_p
105
two bytes
Heat Recovery Leaving Water Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current temperature of the water leaving the heat recovery
section. (A23)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS:-40°–118°C
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
6
Present Value
85
Object Name
HeatRecLvgWaterTemp
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoLvgHRWTemp
Proprietary
temp_p
105
two bytes