ED 15062-7 • MICROTECH II CHILLER CONTROLLER 80
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Oil Feed Temperature
Keypad Menu Path:
Menu
\View
\Comp (4)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
21
Present Value
85
Object Name
OilFeedTemp
Compressor #2
This output network variable indicates the current compressor oil feed temperature for compressor 2. Not available on all chiller
models. (A102)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
83
Present Value
85
Object Name
Comp2OilFeedTemp
LONWORKS
Variable Details
This output network variable indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoOilFeedTemp
Proprietary
temp_p
105
two bytes