Part
2. Functional Specifications
28
Design Guide
DCM014A51
2. The
BACnet
Server in
iTM
sends the new PV to Management Point in
iTM
. The
BACnet
Server in
iTM
then starts a 10 minute timer.
3. If the value in Management Point is changed (i.e., the indoor unit accepted the new value and
sent back the new status to
iTM
), the Management Point in
iTM
sends the new value to the
BACnet
Server in
iTM
. The
BACnet
Server in
iTM
updates the PV and resets the 10 minute
timer.
4. If the value in Management Point is not changed (i.e., the indoor unit did not accept the new
value and did not update the status to
iTM
) nothing happens. When the 10 minute timer
expires, the
BACnet
Server in
iTM
resets to the previous PV.
EXAMPLE 1 – Cool SP Max
Step
BMS
BACnet® Server in
iTM
Management Point in
iTM
Pre-condition
Unocc Cool SP: 80°F
Cool SP range: 70-76°F
Cool Setback SP: 80°F
Cool SP range: 70-76°F
#1
Sets Cool SP max
85°F
PV: 85°F
, previous PV: 76°F
Start 10-min timer
#2
Sends 85°F to Management Point
Cool SP max 85°F is rounded to 78°F
due to Cool Setback SP 80°F.
Cool SP range: 70-
78°F (Changed)
#3
PV 78°F
Reset 10-min timer
Updates 78°F to the BACnet® Server
#1
Sets Cool SP max
85°F again
PV: 85°F
, previous PV: 78°F
Start 10-min timer
#2
Sends 85°F to Management Point
Cool SP max 85°F is rounded to 78°F
due to Cool Setback SP 80°F
Cool SP range: 70-78°F (No change)
#4
When 10-min timer expires, PV
back to 78°F
EXAMPLE 2 – Cool SP
Step
BMS
BACnet® Server in
iTM
Management Point in
iTM
Pre-condition
Cool SP range: 70-78°F
Cool SP: 72°F
Cool SP range: 70-78°F
Cool SP: 72°F
#1
Sets Cool SP 68°F
PV: 68°F
, previous PV: 72°F
Start 10-min timer
#2
Sends 68°F to Management Point
Cool SP 68°F is rounded to 70°F due to
Cool SP range 70-78°F
Cool SP:
70°F (Changed)
#3
PV 70°F
Reset 10-min timer
Sends 70°F to BACnet® Server
#1
Sets Cool SP 68°F
again
PV: 68°F
, previous PV: 70°F
Start 10-min timer
#2
Sends 68°F to Management Point
Cool SP 68°F is rounded to 70°F due to
the Cool SP range 70-78°F
Cool SP: 70°F (No change)
#4
When 10-min timer expires, PV
back to 70°F