Part
2. Functional Specifications
62
Design Guide
DCM014A51
5. Relinquish_Default property is fixed to 16°C/60°F.
6. When subscribed to COV notification, the COV_Increment property is fixed to 1.0 and
cannot be changed.
COV notification is issued when a change of 1°C/1°F or more is detected.
The next COV notification is issued when the temperature further changes for 1°C/1°F or
more from the value of the Present_Value property that triggered the previous COV
notification.
14. Min Setpoint Differential (Cooling & Heating)
Member number: 14
Object name:
Min Setpoint Differential (Cooling & Heating)
Object type:
Analog Value
Description:
Monitors/configures the minimum heating and
cooling setpoint difference for the indoor unit.
Present_Value property:
Minimum heating and cooling setpoint difference on the indoor unit
Notes:
1. The unit is degrees Celsius (°C) or degrees Fahrenheit (°F), depending on the system
settings.
2. The number of significant digits is up to one decimal place for degrees Celsius and zero
decimal places for degrees Fahrenheit.
3. The settable values are fixed by the system (0 to 4[°C] /0 to 7 [°F]).
If a value outside the range is written, it is corrected to the upper/lower limit value.
4. Relinquish_Default property is fixed to 0°C/0°F.
5. When subscribed to COV notification, the COV_Increment property is fixed to 1.0 and
cannot be changed.
COV notification is issued when a change of 1°C/1°F or more is detected.
The next COV notification is issued when the temperature further changes for 1°C/1°F or
more from the value of the Present_Value property that triggered the previous COV
notification.
15. Cooling & Heating Setpoint Tracking Mode
Member number: 15
Object name:
Cooling & Heating Setpoint Tracking Mode
Object type:
Binary Value
Description:
Monitors/configures the status of the tracking
mode for the indoor unit.
Present_Value property:
ACTIVE:
Enable
INACTIVE:
Disable
Note:
1. Relinquish_Default property is fixed to "INACTIVE".