Part
2. Functional Specifications
DCM014A51
Design Guide
75
Description: Monitors the evaporating pressure of the outdoor unit.
Present_Value property:
Evaporating pressure of the outdoor unit
Remarks:
(1) Units are in psi.
(2) The number of valid digits is to two decimal places.
(3) The value range is (-28.45 to 284.47[psi]) (-2.0 to 20.0 [kgf/cm2]
12. M_Condensing Temperature
S1_Condensing Temperature
S2_Condensing Temperature
Member number 102
(
M_Condensing Temperature
)
202
(
S1_Condensing Temperature)
302
(
S2_Condensing Temperature
)
Object name:
M_Condensing Temperature
S1_Condensing Temperature
S2_Condensing Temperature
Object type:
Analog Input
Description:
Monitors the condensing temperature (measured value) of the outdoor
unit.
Present_Value property:
Condensing temperature of the outdoor unit (measured value)
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-65 to 74 [
℃
] / -85 to 165[
゚
F]).
13. M_Evaporating Temperature
S1_Evaporating Temperature
S2_Evaporating Temperature
Member number: 103
(
M_Evaporating Temperature
)
203
(
S1_Evaporating Temperature)
303
(
S2_Evaporating Temperature
)
Object name:
M_Evaporating Temperature
S1_Evaporating Temperature
S2_Evaporating Temperature
Object type:
Analog Input
Description:
Monitors the evaporating temperature (measured value) of the outdoor
unit.
Present_Value property:
Evaporating temperature of the outdoor unit (measured value)
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-79 to 33[
℃
] / -110 to 91[
゚