Follows the iTM software version.
DCM014A51
Design Guide
99
Continued from previous page
Object
Type
Property Identifier
Before (BACnetGW
(Ver6.34.00))
After (
iTM
for North
America)
Property
Device
(for
outdoor
unit)
Object_Name
DAIKIN MasterStation III
Outdoor unit name
System_Status
During D3 initialization:
DOWNLOAD_IN_PROGRE
SS
Fixed to
OPERATIONAL
Normal: OPERATIONAL
Model_Name
Fixed to “D-BACS
BACnet
Gateway”
Fixed to “Outdoor
Unit”
Firmware_Revision
3000
Ver.000.001
Application_Software_Version
3000
*
Protocol_Services_Supported
SubCOV, RP, RPM, WP,
WPM, I-Am, I-Have,
TimeSync, Who-Is, Who-
Has, UTCTimeSync
(DeviceCommunicationCo
ntrol *ver6.20 to )
(AddList, RemoveList
*When Event notification
is supported
RP, RPM, I-Am,
TimeSync,
Who-Is, Who-Has,
UTCTimeSync
Protocol_Object_Types_Supported
AI, AO, AV, BI, BO, BV, MI,
MO,
Device,NotificationClass
AI, BI,MI, Device
Daylight_Saving_Status
Fixed to FALSE
Follows the iTM
clock settings
* Follows the
iTM
software version.