Part
2. Functional Specifications
88
Design Guide
DCM014A51
Continued form previous page
.
#
Indoor Unit Type
Error Code
Description
57
DK_SkyAir
J8
"Malfunction of liquid pipe thermistor (Refrigerant circuit and others)"
58
DK_SkyAir | DK_VRV | DK_RA
J9
"Malfunction of gas pipe thermistor (Refrigerant circuit and others)"
59
DK_SkyAir | DK_VRV
Ja
"Malfunction of high pressure sensor"
60
DK_VRV
JH
"Malfunction of oil temperature thermistor"
61
DK_SkyAir | DK_VRV
JC
"Malfunction of low pressure sensor"
62
DK_VRV
JF
"Malfunction of heating thermistor for heat exchanger"
63
DK_VRV
L0
"Malfunction of inverter system"
64
DK_SkyAir | DK_VRV
L1
"Malfunction of inverter PCB"
65
DK_RA
L3
"Electrical box temperature rise"
66
DK_SkyAir | DK_VRV | DK_RA
L4
"Malfunction of inverter radiating fin temperature rise"
67
DK_SkyAir | DK_VRV | DK_RA
L5
"Inverter instantaneous overcurrent (DC)"
68
DK_VRV
L6
"Inverter instantaneous overcurrent (AC)"
69
DK_SkyAir | DK_VRV
L8
"Overcurrent of inverter compressor"
70
DK_SkyAir | DK_VRV
L9
"Malfunction of inverter compressor startup"
71
DK_VRV
LA
"Malfunction of power transistor"
72
DK_RA
LC
"Malfunction of transmission between OD unit PCB and micro-computer"
73
DK_SkyAir | DK_VRV
LC
"Malfunction of transmission between control and inverter PCB"
74
DK_VRV
P0
"Shortage of refrigerant amount (thermal storage unit)"
75
DK_SkyAir | DK_VRV
P1
"Power voltage imbalance open phase"
76
DK_VRV
P2
"Automatic refrigerant charge operation stop"
77
DK_SkyAir | DK_RA
P3
"Malfunction of thermistor in electrical box"
78
DK_SkyAir | DK_VRV | DK_RA
P4
"Malfunction of radiating fin temperature sensor"
79
DK_VRV
P8
"Heat exchanger freezing protection during automatic refrigerant charging"
80
DK_RA
P9
"Malfunction of fan motor (humidifier unit)"
81
DK_VRV
P9
"Automatic refrigerant charge operation completed"
82
DK_RA
PA
"Broken wire of heater (humidifier unit)"
83
DK_VRV
PA
"Empty refrigerant cylinder during automatic refrigerant charging"
84
DK_RA
PH
"Malfunction of temperature (humidifier unit)"
85
DK_VRV
PH
"Empty refrigerant cylinder during automatic refrigerant charging"
86
DK_VRV
PC
"Empty refrigerant cylinder during automatic refrigerant charging"
87
DK_SkyAir
PJ
"Malfunction of capacity setting (OD unit PCB)"
88
DK_VRV
PJ
"Improper combination between inverter and fan driver"
89
DK_VRV
PE
"Automatic refrigerant charge operation nearly completed"
90
DK_SkyAir | DK_VRV | DK_RA
U0
"Shortage of refrigerant"
91
DK_SkyAir | DK_VRV | DK_RA
U1
"Reverse phase open phase"
92
DK_SkyAir | DK_VRV | DK_RA
U2
"Defect of power supply voltage or instantaneous power failure"
93
DK_VRV
U3
"Check operation not executed"
94
DK_SkyAir | DK_VRV | DK_RA
U4
"Malfunction of transmission between ID and OD unit"
95
DK_SkyAir | DK_VRV | DK_RA
U5
"Malfunction of transmission between ID unit and remote controller"
96
DK_VRV
U6
"Malfunction of transmission between ID units"
97
DK_RA
U7
"Malfunction of transmission between main body micro-computer - INV micro-computer"
98
DK_VRV
U7
"Malfunction of transmission between OD units"
99
DK_SkyAir | DK_VRV
U8
"Malfunction of transmission between remote controllers"
100 DK_VRV
U9
"Malfunction of transmission (other system)"
101 DK_RA
UA
"Defect of ID/OD power supply"
102 DK_SkyAir
UA
"Malfunction of field setting"
103 DK_VRV
UA
"Improper combination of ID and OD units"
104 DK_VRV | DK_RA
UH
"Malfunction of system"
105 DK_SkyAir | DK_VRV
UC
"Malfunction of setting of centralized controller address"
106 DK_VRV
UJ
"Malfunction of transmission (Accessory devices)"
107 DK_SkyAir | DK_VRV
UE
"Malfunction of transmission between ID unit and centralized controller"
108 DK_SkyAir | DK_VRV
UF
"Wiring and piping mismatch"
109 DK_SkyAir | DK_VRV | DK_RA
M1
"Malfunction of centralized remote controller PCB"
110 DK_SkyAir | DK_VRV | DK_RA
M8
"Malfunction of transmission between optional controllers for centralized control"
111 DK_SkyAir | DK_VRV | DK_RA
MA
"Improper combination of optional controllers for centralized control"
112 DK_SkyAir | DK_VRV | DK_RA
MC
"Address duplication improper setting"