Part
2. Functional Specifications
DCM014A51
Design Guide
71
ACTIVE:
Enable
INACTIVE:
Disable
Note:
1. Relinquish_Default property is fixed to "INACTIVE".
3. Timed Override Minutes
Member number: 3
Object name:
Timed Override Minutes
Object type:
Multistate Value
Description:
Monitors/sets the time for the Timer Extension in
iTM
.
Present_Value property:
1: 30 minutes
2: 60 minutes
3: 90 minutes
4: 120 minutes
5: 150 minutes
6: 180 minutes
Note:
1. Relinquish_Default property is fixed to "1".
4. System Forced Off
Member number: 4
Object name:
System Forced off
Object type:
Binary Output
Description:
Executes all emergency stop programs (including the default
program) registered and enabled with the
iTM
.
Present_Value property:
ACTIVE:
Active
INACTIVE:
Inactive
Note:
1. Cancelling the emergency stop programs does not start the indoor units (they remain
stopped). Indoor unit will require a manual restart after the emergency stop switches
from Active to Inactive.
2. Writing INACTIVE does not cancel the emergency stop if the input conditions for
emergency stop are satisfied in the
iTM
.
3. Relinquish_Default property is fixed to "INACTIVE".
4. After an
iTM
reboot, "System Forced Off" is Inactive.
7.4. Individual Outdoor Unit Object Specifications
Outdoor unit common objects
1. Communication Status
Member number: 1
Object name:
Communication Status
Object type:
Binary Input