Part
2. Functional Specifications
68
Design Guide
DCM014A51
INACTIVE:
Off (Thermo-off)
28. Compressor Status
Member number: 28
Object name:
Compressor Status
Object type:
Multistate Input
Description:
Monitors the operating status of the outdoor unit compressor
connected to the indoor unit.
Present_Value property:
1: The outdoor unit compressor connected to
the indoor unit
is stopped (
Off
).
2: The outdoor unit compressor connected to the indoor unit is operating (Oil-return
operation included) (
On
).
3: In heat mode, the outdoor unit compressor connected to the indoor unit is defrosting, in
oil return operating, or the indoor unit is in hot start operation (
Defrost/Hot Start
).
29. Aux Heater Status
Member number: 29
Object name:
Aux Heater Status
Object type:
Binary Input
Description:
Monitors whether or not the auxiliary heater connected to
the indoor unit is operating.
Present_Value property:
ACTIVE:
On
INACTIVE:
Off
30. Forced Thermo-off
Member number: 30
Object name:
Forced Thermo-off
Object type:
Binary Value
Description:
Forcibly restrict the indoor unit thermo-on
Present_Value property:
ACTIVE:
Enable (Forcibly restrict the indoor unit thermo-on).
INACTIVE:
Disable (Cancel the restriction).
Notes:
1. The command is sent to the indoor unit independently regardless if the indoor unit is
operating or stopped.
2. Relinquish_Default property is fixed to "INACTIVE".
31. Indoor Unit Changeover Option
Member number: 31
Object name:
Indoor Unit Changeover Option
Object type:
Binary Input
Description:
Monitors the availability of the Changeover option for an indoor unit.
Present_Value property:
ACTIVE:
Available
INACTIVE:
Not Available (In selecting included)