Part
2. Functional Specifications
DCM014A51
Design Guide
33
Sub-2 Outdoor Unit Points
Instance
No.
Object_Name
Type
Inactive Active
Remarks
Text-1
Text-2
Text-3
Text-4 Text-5 Text-6 Text-7 Text-8
300
S2_Condensing Pressure
AI
*2,*3
301
S2_Evaporating Pressure
AI
*2,*3
302
S2_Condensing
Temperature
AI
*1,*2,*3
303
S2_Evaporating
Temperature
AI
*1,*2,*3
304
S2_Inverter Compressor 1
Speed
AI
*2,*3
305
S2_Inverter Compressor 2
Speed
AI
*2,*3
306
S2_Fan Step
AI
*2,*3
307
S2_EV Position 1
AI
*2,*3
308
S2_EV Position 2
AI
*2,*3
309
S2_Hot Gas Temperature
(Compressor 1)
AI
*1,*2,*3
310
S2_Hot Gas Temperature
(Compressor 2)
AI
*1,*2,*3
311
S2_Liquid Pipe Temperature
AI
*1,*2,*3
312
S2_Liquid Pipe Temperature
(HX Upper)
AI
*1,*2,*3
313
S2_Liquid Pipe Temperature
(HX Lower)
AI
*1,*2,*3
314
S2_Liquid Pipe Temperature
(Deicer)
AI
*1,*2,*3
315
S2_Gas Pipe Temperature
(HX Upper)
AI
*1,*2,*3
316
S2_Gas Pipe Temperature
(HX Lower)
AI
*1,*2,*3
317
S2_Suction Temperature
AI
*1,*2,*3
318
S2_Compressor Suction
Temperature
AI
*1,*2,*3
319
S2_Subcool Inlet
Temperature
AI
*1,*2,*3
320
S2_Subcool Outlet
Temperature
AI
*1,*2,*3
321
S2_Subcool EV Position
AI
*2,*3
*1 The unit of temperature (Celsius or Fahrenheit) follows the
iTM
setting.
*2 The number of valid digits for each object is shown in the table below.
Regarding values from BMS, they are rounded up to the number of significant digits.
(For example, if the value for Electric Power is "25.55", it is rounded up to "25.6")
*3 Objects are not generated for data that does not exist. Depending on the outdoor unit model,
incompatible data may exist. Objects are not generated for such incompatible data.
(Example) If it is a model that has only one main outdoor unit, objects are not generated for Sub-1 or
Sub-2.