Part
3. Commissioning Procedure
DCM014A51
Design Guide
111
3.3. Outdoor Unit Points (for each outdoor unit)
Instance
#
Object Name (Common)
Type
Instance
#
Object Name (Main)
Type
1
Communication Status
BI
100
M_Condensing Pressure
AI
2
Operation Mode
MI
101
M_Evaporating Pressure
AI
3
Outdoor Unit Alarm Status
BI
102
M_Condensing Temperature
AI
4
Defrost Mode
BI
103
M_Evaporating Temperature
AI
5
Oil Return
BI
104
M_Inverter Compressor 1 Speed
AI
6
Electric Power
AI
105
M_Inverter Compressor 2 Speed
AI
7
Electric Current
AI
106
M_Fan Step
AI
8
System Capacity Code
AI
107
M_EV Position 1
AI
9
Outdoor Air Temperature
AI
108
M_EV Position 2
AI
109
M_Hot Gas Temperature
(Compressor 1)
AI
110
M_Hot Gas Temperature
(Compressor 2)
AI
111
M_Liquid Pipe Temperature
AI
112
M_Liquid Pipe Temperature (HX
Upper)
AI
113
M_Liquid Pipe Temperature
(HX Lower)
AI
114
M_Liquid Pipe Temperature
(Deicer)
AI
115
M_Gas Pipe Temperature
(HX Upper)
AI
116
M_Gas Pipe Temperature
(HX Lower)
AI
117
M_Suction Temperature
AI
118
M_Compressor Suction
Temperature
AI
119
M_Subcool Inlet Temperature
AI
120
M_Subcool Outlet Temperature
AI
121
M_Subcool EV Position
AI
Note: Shaded points are not available by default and will need to be enabled during the
iTM
BACnet®
Server Gateway commissioning.