Part
2. Functional Specifications
32
Design Guide
DCM014A51
Sub-1 Outdoor Unit Points
Instance
No.
Object_Name
Type
Inactive Active
Remarks
Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Text-7 Text-8
200
S1_Condensing Pressure
AI
*2,*3
201
S1_Evaporating Pressure
AI
*2,*3
202
S1_Condensing Temperature
AI
*1,*2,*3
203
S1_Evaporating Temperature
AI
*1,*2,*3
204
S1_Inverter Compressor 1 Speed
AI
*2,*3
205
S1_Inverter Compressor 2 Speed
AI
*2,*3
206
S1_Fan Step
AI
*2,*3
207
S1_EV Position 1
AI
*2,*3
208
S1_EV Position 2
AI
*2,*3
209
S1_Hot Gas Temperature
(Compressor 1)
AI
*1,*2,*3
210
S1_Hot Gas Temperature
(Compressor 2)
AI
*1,*2,*3
211
S1_Liquid Pipe Temperature
AI
*1,*2,*3
212
S1_Liquid Pipe Temperature (HX
Upper)
AI
*1,*2,*3
213
S1_Liquid Pipe Temperature (HX
Lower)
AI
*1,*2,*3
214
S1_Liquid Pipe Temperature
(Deicer)
AI
*1,*2,*3
215
S1_Gas Pipe Temperature (HX
Upper)
AI
*1,*2,*3
216
S1_Gas Pipe Temperature (HX
Lower)
AI
*1,*2,*3
217
S1_Suction Temperature
AI
*1,*2,*3
218
S1_Compressor Suction
Temperature
AI
*1,*2,*3
219
S1_Subcool Inlet Temperature
AI
*1,*2,*3
220
S1_Subcool Outlet Temperature
AI
*1,*2,*3
221
S1_Subcool EV Position
AI
*2,*3