Part
2. Functional Specifications
DCM014A51
Design Guide
85
The COV notification support for each object is as follows:
Indoor unit device System control device
Instance
Number
Object_Name
Type
Instance
Number
Object_Name
Type
1
Occupancy Mode
MO
1
Enable
ITM
Schedule Operation
BO
2
Unit On_Off Status
BI
2
Enable
ITM
Auto Changeover
Operation
BO
3
Alarm Status
BI
3
Timed Override Minutes
MV
4
Operation Mode
MV
4
System Forced Off
BO
5
Room Temperature
AI
6
Occ Cooling Setpoint
AV
7
Occ Heating Setpoint
AV
8
Unocc Cooling Setpoint
AV
9
Unocc Heating Setpoint
AV
10
Max Cooling Setpoint
AV
11
Min Cooling Setpoint
AV
12
Max Heating Setpoint
AV
13
Min Heating Setpoint
AV
14
Min Setpoint Differential (Cooling &
Heating)
AV
15
Cooling & Heating Setpoint Tracking
Mode
BV
16
Fan Speed
MV
17
Airflow Direction
MV
18
Timed Override Operation
BV
19
Current Unit Operation
MI
20
Remote Controller Prohibit (On_Off)
MV
21
Remote Controller Prohibit
(Operation Mode)
BV
22
Remote Controller Prohibit (Setpoint)
BV
23
Filter Sign Status
BI
24
Filter Sign Reset
BV
25
Indoor Fan Status
BI
26
Communication Status
BI
27
Thermo-on Status
BI
28
Compressor Status
MI
29
Aux Heater Status
BI
30
Forced Thermo-off
BV
31
Indoor Unit Changeover Option
BI