Part
2. Functional Specifications
DCM014A51
Design Guide
77
Description:
Monitors the fan step of the outdoor unit.
Present_Value property:
Fan step of the outdoor unit
Remarks:
(1) There are no units of measurement.
(2) The number of valid digits is an integer.
(3) The value range is (0 to 8) for
VRV
IV, and (0 to 255) for
VRV
IV R.
17. M_EV Position 1
S1_EV Position 1
S2_EV Position 1
Member number: 107
(
M_EV Position 1
)
207
(
S1_EV Position 1)
307
(
S2_EV Position 1
)
Object name:
M_EV Position 1
S1_EV Position 1
S2_EV Position 1
Object type:
Analog Input
Description:
Monitors the EV position of the outdoor unit (upper side).
Present_Value property:
EV position of the outdoor unit (upper side)
Remarks:
(1) There are no units of measurement.
(2) The number of valid digits is an integer.
(3) The value range is (0 to 3000).
18. M_EV Position 2
S1_EV Position 2
S2_EV Position 2
Member number: 108
(
M_EV Position 2
)
208
(
S1_EV Position 2)
308
(
S2_EV Position 2
)
Object name:
M_EV Position 2
S1_EV Position 2
S2_EV Position 2
Object type:
Analog Input
Description:
Monitors the EV position of the outdoor unit (lower side).
Present_Value property:
EV position of the outdoor unit (lower side)
Remarks:
(1) There are no units of measurement.
(2) The number of valid digits is an integer.
(3) The value range is (0 to 3000).