Description:
Monitors the temperature of the outdoor unit liquid pipe heat
exchanger.
Present_Value property:
Temperature of the outdoor unit liquid pipe heat exchanger
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-50 to 120[
℃
] / -58 to 248[
゚
F]).
22. M_Liquid Pipe Temperature (HX Upper)
S1_Liquid Pipe Temperature (HX Upper)
S2_Liquid Pipe Temperature (HX Upper)
Member number: 112
(
M_Liquid Pipe Temperature (HX Upper)
)
212
(
S1_Liquid Pipe Temperature (HX Upper))
312
(
S2_Liquid Pipe Temperature (HX Upper)
)
Object name:
M_Liquid Pipe Temperature (HX Upper)
S1_Liquid Pipe Temperature (HX Upper)
S2_Liquid Pipe Temperature (HX Upper)
Object type:
Analog Input
Description:
Monitors the temperature of the outdoor unit liquid pipe heat
exchanger (upper side).
Present_Value property:
Temperature of the outdoor unit liquid pipe heat exchanger (upper
side)
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-50 to 120[
℃
] / -58 to 248[
゚
F])
23. M_Liquid Pipe Temperature (HX Lower)
S1_Liquid Pipe Temperature (HX Lower)
S2_Liquid Pipe Temperature (HX Lower)
Member number: 113
(
M_Liquid Pipe Temperature (HX Lower)
)
213
(
S1_Liquid Pipe Temperature (HX Lower))
313
(
S2_Liquid Pipe Temperature (HX Lower)
)
Object name:
M_Liquid Pipe Temperature (HX Lower)
S1_Liquid Pipe Temperature (HX Lower)
S2_Liquid Pipe Temperature (HX Lower)
Object type:
Analog Input
Description:
Monitors the temperature of the outdoor unit liquid pipe heat
exchanger (lower side).
Present_Value property:
Temperature of the outdoor unit liquid pipe heat exchanger (lower
side)
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.