Part
5. Installation Manual
DCM014A51
Design Guide
139
Appendix B. Supported Indoor Unit Models and Monitoring Control
Items
The following table includes a list of objects for each of the supported indoor unit models compatible
with the
iTM
BACnet® Server Gateway function.
Instance
No.
Object Name
VRV
Indoor
Unit
SkyAir
Indoor Unit
(except
FTXS)
Outdoor Air
Processing
Unit
Mini-Split &
SkyAir
FTXS Indoor
Units
(KRP928)
FFQ Indoor Unit
for Multi-Split &
Super Multi Plus
(DTA112BA51
adaptor may be
required)
1
Occupancy Mode
✓
✓
(Note4)
✓
(Note4)
✓
(Note4)
✓
(Note4)
2
Unit On_Off Status
✓
✓
✓
✓
✓
3
Alarm Status
✓
✓
✓
✓
✓
4
Operation Mode
✓
✓
✓
✓
(Note3)
✓
5
Room Temperature
✓
✓
✓
(return air
temp)
✓
✓
6
Occ Cooling Setpoint
✓
✓
N/A
✓
(Note1,2)
✓
7
Occ Heating Setpoint
✓
✓
N/A
✓
(Note1,2)
✓
8
Unocc Cooling Setpoint
✓
✓
N/A
✓
✓
9
Unocc Heating Setpoint
✓
✓
N/A
✓
✓
10
Max Cooling Setpoint
✓
✓
N/A
✓
✓
11
Min Cooling Setpoint
✓
✓
N/A
✓
✓
12
Max Heating Setpoint
✓
✓
N/A
✓
✓
13
Min Heating Setpoint
✓
✓
N/A
✓
✓
14
Min Setpoint Differential
(Cooling & Heating)
✓
✓
N/A
✓
✓
15
Cooling & Heating Setpoint
Tracking Mode
✓
✓
N/A
✓
✓
16
Fan Speed
✓
✓
N/A
N/A
✓
17
Airflow Direction
✓
✓
N/A
N/A
✓
18
Timed Override Operation
✓
✓
✓
✓
✓
19
Current Unit Operation
✓
✓
✓
✓
✓
20
Remote Controller Prohibit
(On_Off)
✓
✓
✓
✓
✓
21
Remote Controller Prohibit
(Operation Mode)
✓
✓
✓
✓
✓
22
Remote Controller Prohibit
(Setpoint)
✓
✓
N/A
✓
✓
23
Filter Sign Status
✓
✓
✓
N/A
✓
24
Filter Sign Reset
✓
✓
✓
N/A
✓
25
Indoor Fan Status
✓
✓
✓
N/A
✓
26
Communication Status
✓
✓
✓
✓
✓
27
Thermo-on Status
✓
✓
✓
N/A
✓
28
Compressor Status
✓
✓
✓
N/A
✓
29
Aux Heater Status
✓
✓
✓
N/A
✓
30
Forced Thermo-off
✓
✓
✓
N/A
✓
31
Indoor Unit Changeover Option
✓
✓
✓
✓
✓