Part
2. Functional Specifications
78
Design Guide
DCM014A51
19. M_Hot Gas Temperature (Compressor 1)
S1_Hot Gas Temperature (Compressor 1)
S2_Hot Gas Temperature (Compressor 1)
Member number: 109
(
M_Hot Gas Temperature (Compressor 1)
209
(
S1_Hot Gas Temperature (Compressor 1))
309
(
S2_Hot Gas Temperature (Compressor 1)
Object name:
M_Hot Gas Temperature (Compressor 1)
S1_Hot Gas Temperature (Compressor 1)
S2_Hot Gas Temperature (Compressor 1)
Object type:
Analog Input
Description:
Monitors the temperature 1 of outdoor unit discharge pipe.
Present_Value property:
Outdoor unit discharge pipe temperature 1
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (0 to 255[
℃
] / 32 to 491[
゚
F]).
20. M_Hot Gas Temperature (Compressor 2)
S1_Hot Gas Temperature (Compressor 2)
S2_Hot Gas Temperature (Compressor 2)
Member number: 110
(
M_Hot Gas Temperature (Compressor 2
)
210
(
S1_Hot Gas Temperature (Compressor 2))
310
(
S2_Hot Gas Temperature (Compressor 2)
Object name:
M_Hot Gas Temperature (Compressor 2)
S1_Hot Gas Temperature (Compressor 2)
S2_Hot Gas Temperature (Compressor 2)
Object type:
Analog Input
Description:
Monitors the temperature 2 of outdoor unit discharge pipe.
Present_Value property:
Outdoor unit discharge pipe temperature 2
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (0 to 255[
℃
] / 32 to 491[
゚
F]).
21. M_Liquid Pipe Temperature
S1_Liquid Pipe Temperature
S2_Liquid Pipe Temperature
Member number: 111
(
M_Liquid Pipe Temperature
)
211
(
S1_Liquid Pipe Temperature)
311
(
S2_Liquid Pipe Temperature
)
Object name:
M_Liquid Pipe Temperature
S1_Liquid Pipe Temperature
S2_Liquid Pipe Temperature
Object type:
Analog Input