Part
2. Functional Specifications
DCM014A51
Design Guide
69
32. Return Air Temperature
Member number: 32
Object name:
Return Air Temperature
Object type:
Analog Input
Description:
Monitors the return air temperature of the indoor unit.
Present_Value property:
Return air temperature of the indoor unit.
Remarks:
(1) Units are set to
℃
/
o
F depending on the system settings.
(2) The number of valid digits is to one decimal place for both Celsius and Fahrenheit.
(3) The value range is (-50.0 to 120.0[
℃
] / -58.0 to 248.0[
゚
F]).
33. Discharge Air Temperature
Member number: 33
Object name:
Discharge Air Temperature
Object type:
Analog Input
Description:
Monitors the discharge air temperature of the indoor unit.
Present_Value property:
Discharge air temperature of the indoor unit
Remarks:
(1) Units are set to
℃
/
o
F depending on the system settings.
(2) The number of valid digits is to one decimal place for both Celsius and Fahrenheit.
(3) The value range is (-50.0 to 120.0[
℃
] / -58.0 to 248.0[
゚
F]).
34. Liquid Pipe Temperature
Member number: 34
Object name:
Liquid Pipe Temperature
Object type:
Analog Input
Description:
Monitors the liquid pipe temperature of the indoor unit.
Present_Value property:
Liquid pipe temperature of the indoor unit
Remarks:
(1) Units are set to
℃
/
o
F depending on the system settings.
(2) The number of valid digits is to one decimal place for both Celsius and Fahrenheit.
(3) The value range is (-50.0 to 120.0[
℃
] / -58.0 to 248.0[
゚
F]).
35
.
Gas Pipe Temperature
Member number: 35
Object name:
Gas Pipe Temperature
Object type:
Analog Input
Description:
Monitors the gas pipe temperature of the indoor unit.
Present_Value property:
Gas pipe temperature of the indoor unit
Remarks:
(1) Units are set to
℃
/
o
F depending on the system settings.
(2) The number of valid digits is to one decimal place for both Celsius and Fahrenheit.