・Time
_Of_Active_Time_Reset
98
Design Guide
DCM014A51
12.2. Functions changed from BACnetGW
Services changed because COV and Event are not supported.
Object
Type
Property Identifier
Before (BACnetGW
(Ver6.34.00))
After (
iTM
for North
America)
Property
Device
(for
indoor
unit)
Object_Name
DAIKIN MasterStation III
Indoor unit name
System_Status
During D3 initialization:
DOWNLOAD_IN_PROGRESS
Fixed to
OPERATIONAL
Model_Name
Fixed to "D-BACS
BACnet
Gateway"
Fixed to "Indoor
Unit"
Firmware_Revision
3000
Ver.000.001
Application_Software_Version
3000
*
Protocol_Services_Supported
SubCOV, RP, RPM, WP, WPM,
I-Am, I-Have, TimeSync, Who-
Is, Who-Has, UTCTimeSync
(DeviceCommunicationControl
*ver6.20 to)
(AddList, RemoveList *When
Event notification is
supported)
SubCOV, RP, RPM,
WP, WPM, I-Am,
TimeSync, Who-Is,
Who-Has,
UTCTimeSync
Protocol_Object_Types_Supported
AI, AO, AV, BI, BO, BV, MI,
MO, Device,NotificationClass
AI, AV, BI,BV, MI,
MO, MV, Device
Daylight_Saving_Status
Fixed to FALSE
Follows the iTM
clock settings
Device
(for
system
control )
Object_Name
DAIKIN MasterStation III
Fixed to “Daikin ITM
Server Control”
System_Status
During D3 initialization:
DOWNLOAD_IN_PROGRESS
Normal: OPERATIONAL
Fixed to
OPERATIONAL
Model_Name
Fixed to “D-BACS
BACnet
Gateway”
Fixed to “Daikin ITM
Server Control”
Firmware_Revision
3000
Ver.000.001
Application_Software_Version
3000
*
Protocol_Services_Supported
SubCOV, RP, RPM, WP, WPM,
I-Am, I-Have, TimeSync, Who-
Is, Who-Has, UTCTimeSync
(DeviceCommunicationControl
*ver6.20 to)
(AddList, RemoveList *When
Event notification is
supported)
SubCOV, RP, RPM,
WP, WPM, I-Am,
TimeSync, Who-Is,
Who-Has,
UTCTimeSync
Protocol_Object_Types_Supported
AI, AO, AV, BI, BO, BV, MI,
MO, Device,NotificationClass
BO, MV, Device
Daylight_Saving_Status
Fixed to FALSE
Follows the iTM
clock settings