Basic Control
ESiEN09-06 A
28
Function
2.4
Outdoor Unit Fan Control in Cooling Operation
While in cooling operation, if the outdoor temperature is low, this mode provides high-pressure
control using the outdoor unit fan to retain appropriate liquid pressure, thus ensuring refrigerant
circulation rate to be supplied to AHU.
Upper limit of fan
revolutions: Step 8
Upper limit of outdoor unit
fan revolutions
Step 7
-1 step on
outdoor unit fan
+1 step on
outdoor unit fan
Pc
<2.75MPa
PI control
Pc
>3.24MPa
Lapse of 20 sec.
PI control
PI control
*For fan revolutions in each step,
refer to information on page 107.
Lapse of 20 sec.
Hold the
current step on
outdoor unit fan