ESiEN09-06 A
Combination Table
General Information
5
2. Combination Table
Heat pump
P: Pair: Combination depending on AHU heat exchanger volume and capacity.
Control box
Expansion valve kit
Outdoor unit
EKEQDCBV3 EKEQFCBV3 EKEXV63 EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250
three
phase
ERQ125
P
P
P
P
P
P
P
-
-
ERQ200
P
P
-
-
P
P
P
P
P
ERQ250
P
P
-
-
-
P
P
P
P
Allowed heat exchanger
capacity - COOLING(kW)
Allowed heat exchanger
capacity - HEATING(kW)
Minimum
Maximum
Minimum
Maximum
Cap
class
EXV
EKEXV50
5,0
6,2
5,6
7,0
EKEXV63
6,3
7,8
7,1
8,8
EKEXV80
7,9
9,9
8,9
11,1
EKEXV100
10,0
12,3
11,2
13,8
EKEXV125
12,4
15,4
13,9
17,3
EKEXV140
15,5
17,6
17,4
19,8
EKEXV200
17,7
24,6
19,9
27,7
EKEXV250
24,7
30,8
27,8
34,7
EKEXV400
35,4
49,5
39,8
55,0
EKEXV500
49,6
61,6
55,1
69,3
Cooling saturated suction temp. (SST) = 6°C
Air temperature = 27°C DB / 19°C WB
Superheat (SH) = 5 K
Heating saturated suction temp. (SST) = 46°C
Air temperature = 20°C DB
Subcool (SC) = 3 K
Summary of Contents for ERQ Series
Page 2: ......
Page 16: ...Combination Table ESiEN09 06 A 6 General Information...
Page 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Page 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Page 58: ...Outline of Control ESiEN09 06 A 48 Function...
Page 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Page 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...