Field Setting
Test Operation
121
Heating: Upper & lower limit of T
c
can be chosen
(6.3) Y-control
Since there is no external input to change the T
e
/T
c
value, their values can only be changed by
local setup by means of the Daikin remote controller (during installation).
Cooling: T
e
setting
Heating: T
c
setting
(7) Renewal of Target Refrigerant Temperature (W- & X-control)
When a level of the main pcb is updated, the T
e
/T
c
value of the outdoor is updated
simultaneously, otherwise the T
e
/T
c
value remains constant.
When the DDC level remains constant for A seconds, a level update is executed in the main
pcb.
For X-control:
Mode n° setting
Setting switch n° Setting position n°
Setting
Lower limit T
c
(°C)
Upper limit T
c
(°C)
51
0
00
30
55
01
35
55
02
40
55
03
43
55
04
30
50
05
35
50
06
40
50
07
43
50
08
30
49
09
35
49
10
40
49
11
43
49
12
30
45
13
35
45
14
40
45
15
43
45
Mode n° setting
Setting switch n° Setting position n°
Setting
23 (13)
1
01
T
e
= 5°C
02
T
e
= 6°C
03
T
e
= 7°C
04
T
e
= 8°C
05
T
e
= 9°C
06
T
e
= 10°C
07
T
e
= 11°C
08
T
e
= 12°C
2
01
T
c
= 43°C
02
T
c
= 44°C
03
T
c
= 45°C
04
T
c
= 46°C
05
T
c
= 47°C
06
T
c
= 48°C
07
T
c
= 49°C
Mode n° setting
Setting switch n° Setting position n°
Setting
20 (10)
4
01
A = 60 sec
02
A = 120 sec
03
A = 180 sec
04
A = 240 sec
Summary of Contents for ERQ Series
Page 2: ......
Page 16: ...Combination Table ESiEN09 06 A 6 General Information...
Page 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Page 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Page 58: ...Outline of Control ESiEN09 06 A 48 Function...
Page 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Page 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...