ESiEN09-06 A
Basic Control
Function
27
2.3
Step Control of Outdoor Unit Fans
Used to control the revolutions of outdoor unit fans in the steps listed in table below, according
to condition changes.
*
Figures listed above are all those controlled while in standard mode, which vary when the
system is set to high static pressure or capacity precedence mode.
STEP
No.
Fan revolutions (rpm)
ERQ 125
ERQ 200
ERQ 250
0
0
0
0
1
285
350
350
2
315
370
370
3
360
400
400
4
450
450
460
5
570
540
560
6
710
670
680
7
Cooling: 951
Heating: 941
760
Cooling: 821
Heating: 800
8
Cooling: 951
Heating: 941
Cooling: 796
Heating: 780
Cooling: 821
Heating: 800