Model Names of Outdoor Unit, Control Box and Expansion Valve Kit
ESiEN09-06 A
4
General Information
1.3
Expansion Valve Kit
Outlook
Expansion valve kit installation drawing:
Model name
Limits for outdoor unit (expansion valve kit).
Depending on the heat exchanger, a connectable EKEXV (expansion valve kit) must be
selected to these limitations.
Saturated suction temperature (SST) = 6°C, SH (superheat) = 5 K, air temperature = 27°C DB /
19°C WB.
Outdoor unit (class)
EKEXV kit
125
EKEXV63~140
200
EKEXV100~250
250
EKEXV125~250
Allowed heat exchanger volume (dm
3
) Allowed heat exchanger capacity (kW)
EKEXV class
Minimum
Maximum
Minimum
Maximum
63
1.66
2.08
6.3
7.8
80
2.09
2.64
7.9
9.9
100
2.65
3.30
10.0
12.3
125
3.31
4.12
12.4
15.4
140
4.13
4.62
15.5
17.6
200
4.63
6.60
17.7
24.6
250
6.61
8.25
24.7
30.8