ESiEN09-06 A
Specifications
Specifications
9
Operation
range
Cooling
Min
°CDB
-5
Max
°CDB
43
Heating
Min
°CWB
-20
Max
°CWB
15
Sound level
(nominal)
Sound power
dBA
72
78
Sound pressure
dBA
54
57
58
Refrigerant
Type
R-410A
Charge
kg
6,2
7,7
8,4
Control
Electronic expansion valve
Nr of circuits
1
Refrigerant oil Type
Synthetic (ether) oil
Charged volume
l
1,7
2,1
4,3
Piping
connections
Liquid
Type
Brazing connection
Diameter
(OD)
mm
9,52
Gas
Type
Brazing connection
Diameter
(OD)
mm
15,9
19,1
22,2
Discharge gas Type
Diameter
(OD)
mm
Drain
Quantity
Diameter
(OD)
mm
Heat insulation
Both liquid and gas
Max total length
m
55
Defrost method
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Capacity control method
Inverter controlled
Capacity control [%]
~ 100
Safety devices
High pressure switch
Fan driver overload protector
Overcurrent relay
Inverter overload protector
PC board fuse
Standard
accessories
Item
Installation manual
Quantity
1
Standard
accessories
Item
Operation manual
Quantity
1
Standard
accessories
Item
Connection pipes
Quantity
4
Notes
Nominal cooling capacities are based on: indoor temperature: 27°CDB/19°CWB, outdoor temperature: 35°CDB,
equivalent refrigerant piping: 7,5m, level difference: 0m.
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB/6°CWB,
equivalent refrigerant piping: 7,5m, level difference: 0m.
Sound power level is an absolute value that a sound generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details,
please refer to sound level drawings.
Sound values are measured in a semi-anechoic room.
ELECTRICAL SPECIFICATIONS
ERQ125A7W1B
ERQ200A7W1B
ERQ250A7W1B
Power supply Name
W1
Phase
3N~
Frequency
Hz
50
Voltage
V
400
Current
Nominal
running
current (RLA)
Cooling
A
5,1
7,5
11,3
Heating
A
5,8
8,2
11,1
Starting current (MSC)
A
74
Zmax
-
0,27
Minimum Ssc value
kVA
-
889
842
Min circuit amps (MCA)
A
11,9
18,5
21,6
Max fuse amps (MFA)
A
16
25
Total overcurrent amps
(TOCA)
A
15,6
16,5
31,5
Full load amps (FLA)
A
0,4
0,7
0,9
Voltage range
V
400 ±10%
Wiring
connections
For power
supply
Quantity
5
Remark
Earth wire included
For
connection
with indoor
Quantity
2
Remark
F1 - F2
Power supply intake
Both AHU and outdoor unit
TECHNICAL SPECIFICATIONS
ERQ125A7W1B
ERQ200A7W1B
ERQ250A7W1B
Summary of Contents for ERQ Series
Page 2: ......
Page 16: ...Combination Table ESiEN09 06 A 6 General Information...
Page 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Page 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Page 58: ...Outline of Control ESiEN09 06 A 48 Function...
Page 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Page 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...