Other Control
ESiEN09-06 A
42
Function
5.1.2 Principle
[Set the system to operation prohibition mode by compressor]
• In order to set an INV compressor to operation
prohibition mode, set No. 42 of Setting mode 2 to
"EMERGENCY OPERATION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 42 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• In order to set STD1 compressor to operation
prohibition mode, set No. 19 of Setting mode 2 to
"STD1 OPERATION PROHIBITION". (ERQ 250
A7W1B)
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
LED display ( :ON
:OFF
:Blink)
H1P----H7P
(Factory set)
LED display ( :ON
:OFF
:Blink)
H1P----H7P
(Factory set)