Protection Control
ESiEN09-06 A
38
Function
4.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
[INV compressor]
[STD compressor]
• HTds>120˚C continues for 5 min. or more.
• HTds>135˚C
• Tp>135˚C continues for 10 min. or more.
• Tp>145˚C
or
Applicable STD
compressor stops.
After 10 min.
Discharge pipe temp.
protection control not limited
HTds : Value of STD compressor discharge
pipe temperature ( Tds) compensated
with outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.