Field Setting
ESiEN09-06 A
114
Test Operation
3. Field Setting
3.1
Field Setting from Remote Controller
Individual function of AHU can be changed from the remote controller. At the time of installation
or after service inspection / repair, make the local setting in accordance with the following
description.
Wrong setting may cause malfunction.
3.1.1 Wired Remote Controller
BRC1D528
1. When in the normal mode, press the “
” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “
” button.
3. Push the “
” upper button and select FIRST CODE NO.
4. Push the “
” lower button and select the SECOND CODE NO.
5. Push the “
” button once and the present settings are SET.
6. Push the “
” button to return to the NORMAL MODE.
Notes :
1. Do not make any settings not given in the table.
2. Not displayed if the AHU is not equipped with that function.
3. When returning to the normal mode, “88” may be displayed in the LCD in order for the
remote controller to initialize itself.
Summary of Contents for ERQ Series
Page 2: ......
Page 16: ...Combination Table ESiEN09 06 A 6 General Information...
Page 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Page 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Page 58: ...Outline of Control ESiEN09 06 A 48 Function...
Page 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Page 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...